When PID control is to be performed using the same unit and scale as of feedback values, the
J105 and J205 settings need not be changed. (Factory default: The unit and scale for feedback
values are used.)
Set here when PID control is to be performed using a unit and scale which are different from
those for feedback values.
- Data setting range: 1 to 80
Data for
Display unit
J105/J205
0: Inherit * (Factory default)
1
No unit
2
%
4
r/min
7
kW
3
20
m
/s (flow quantity)
3
21
m
/min (flow quantity)
3
22
m
/h (flow quantity)
* The unit and scale for feedback values are used.
For feedback value selection, see function codes E61 to E63.
The table below shows function codes to be used for setting a unit and scale for
feedback values.
Terminal [12]
Terminal [C1]
Terminal [V2]
J106
PID Control 1 (Maximum scale, Minimum scale)
J107
PID control values can be converted into easily recognizable physical quantity and displayed.
Set PID control 1 with function codes J106 and J107 and PID control 2 with function codes
J205 and J207.
Set the maximum scale "PID command value/ display for 100% of a PID feedback value"
with J106 and J206, and the minimum scale "PID command value/ display for 0% of a PID
feedback value" with J107 and J207.
Values to be displayed are as below.
Display value = (PID command value or PID feedback value (%))/100 x (Maximum scale -
Minimum scale) + Minimum scale
- Data setting range: (Maximum scale and minimum scale) -999.00 to 0.00 to 9990.00
Data for
Display unit
J105/J205
23
L/s (flow quantity)
24
L/min (flow quantity)
25
L/h (flow quantity)
40
Pa (pressure)
41
kPa (pressure)
42
MPa (pressure)
43
mbar (pressure)
44
bar (pressure)
Display unit
C58
C64
C70
J206, J207 (PID Control 2 (Maximum scale, Minimum scale))
6-191
6.3 Details of Function Codes
Data for
Display unit
J105/J205
45
mmHg (pressure)
46
Psi (pressure)
47
mWG (pressure)
48
inWG (pressure)
60
K (temperature)
61
°C (temperature)
62
°F (temperature)
80
ppm (density)
Maximum scale
Minimum scale
C59
C65
C71
C60
C66
C72