  • Page 1 Instruction Manual Non-Bypass Panels FRENIC-EcoPAK Fuji Electric Corp. of America FECA-IN-106 / 122010 Information subject to change without notice. Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com...
  • Page 2: Safety Precautions

    Safety Precautions Read this manual thoroughly before proceeding with installation, connections (wiring), or maintenance and inspection. Ensure you have sound knowledge of the device and familiarize yourself with all safety information and precautions before proceeding to operate the drive. Refer to the drive instruction manual (INR-SI47-1225-E) FRENIC-Eco for further safety information.
  • Page 3 FRENIC-EcoPAK Non-Bypass Panel Overview non-bypass panel is a packaged drive solution in a Type 1 FRENIC-EcoPAK enclosure. NEMA 12 ventilated enclosure is available as an option. Features  Type 1 enclosure with “space-saving” footprint  Metallic enclosures to reduce radio frequency interference (RFI) ...
  • Page 4: Panel Identification

    Panel Identification Each panel has a nameplate label, like the example pictured above, FRENIC-EcoPAK which contains important information about the panel. This label is located on the inside of the hinged door on the enclosure. CAUTION  Refer to the nameplate label to determine the panel input voltage and current requirements prior to installation and wiring.
  • Page 5: Installation

    Installation CAUTION panel should be located indoors: FRENIC-EcoPAK  Away from flammable or combustible liquids, gases, and other materials  Away from sources of dust, metal shavings, or other particulate material  Away from liquids, spray, or mist  Away from sources of heat ...
  • Page 6: Wiring Overview

    Wiring Overview panel must be connected to an input power source, a motor FRENIC-EcoPAK (output power), and control signals. WARNING  Wiring should be performed by a qualified electrician using standard practices as specified by local and national codes. ...
  • Page 7 Wiring Overview (cont’d) UL/NEMA Type 1 UL/NEMA Type 1 2-10Hp @ 208/230V 15-20Hp @ 208/230V 2-20Hp @ 460V 25-40Hp @ 460V Page 7 of 22 Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com...
  • Page 8 Wiring Overview (cont’d) NEMA 12 Ventilated NEMA 12 Ventilated 2-30Hp @ 208/230V 40Hp @ 208/230V 2-40Hp @ 460V 50-75Hp @ 460V Page 8 of 22 Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com...
  • Page 9 Wiring Overview (cont’d) UL/NEMA Type 1 UL/NEMA Type 1 25-30Hp @ 208/230V 40-60Hp @ 208/230V 50-75Hp @ 460V 100-200Hp @ 460V NEMA 12 Ventilated 50-60Hp @ 208/230V 100-200Hp @ 460V Page 9 of 22 Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com...
  • Page 10: Control Wiring

    All control wiring, except the damper control output and the programmable relay outputs, connects to the terminals on the drive. The following diagram shows control connections that are available on panels: FRENIC-EcoPAK Description of Control Connections  Damper Control output (DMPRLY):...
  • Page 11 Field Wiring Torque and Wire Size Values for 208/230V FRENIC-EcoPAK Circuit Breaker Fusible Disconnect Terminal Blocks 'CB' 'FUSDISC' 'CTB' 17 in.lb. 4.5 in.lb. 18-8 AWG 22-12 AWG 17 in.lb. 4.5 in.lb. 18-8 AWG 22-12 AWG 17 in.lb. 4.5 in.lb. 18-8 AWG 22-12 AWG 62 in.lb.
  • Page 12 Field Wiring Torque and Wire Size Values for 460V FRENIC-EcoPAK Circuit Breaker Fusible Disconnect Terminal Blocks 'CB' 'FUSDISC' 'CTB' 17 in.lb. 4.5 in.lb. 18-8 AWG 22-12 AWG 17 in.lb. 4.5 in.lb. 18-8 AWG 22-12 AWG 17 in.lb. 4.5 in.lb. 18-8 AWG 22-12 AWG 17 in.lb.
  • Page 13 BASIC PANEL STARTUP CAUTION  Make sure all power and control wiring is completed before proceeding.  As with all electrical equipment installations, insure all safety/wiring instructions have been followed in accordance with this product’s manuals and local and national codes.
  • Page 14 (INR-SI47-1225-E) for more information. panel was intended to be integrated into a building automation FRENIC-EcoPAK system and controlled by remote signals. If these signals are not available, the panel can be set up to be operated locally. Follow these steps to set the panel up for local operation: 1.
  • Page 15: Common Parameter Settings

    COMMON PARAMETER SETTINGS Also refer to the drive instruction manual (INR-SI47-1225-E) for more FRENIC-Eco information. Factory-set drive parameters and settings These parameters and settings are pre-set from the factory for the panel to be operational. If, for some reason, the drive parameters are reinitialized, these parameters must be reset for correct panel operation.
  • Page 16 Programming the Drive FRENIC-Eco Also refer to Chapter 3 in the drive instruction manual (INR-SI47-1225-E) FRENIC-Eco for more information. Page 16 of 22 Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com...
  • Page 17 Programming the Drive FRENIC-Eco (cont’d) To set drive parameters using the keypad, first make sure the drive is stopped. Parameters cannot be changed while the drive is running. To enter the programming menu, press the Program Key (PRG) on the keypad. To return to the previous screen, press either (PRG) or (RESET).
  • Page 18: Operation

    OPERATION Operator Controls panel includes the following controls for local operation and FRENIC-EcoPAK monitoring:  Main power disconnect  Drive keypad panel includes the following controls for remote operation and FRENIC-EcoPAK monitoring:  Analog speed reference input  Analog monitor output ...
  • Page 19: Periodic Maintenance

    MAINTENANCE Periodic Maintenance The following items require periodic inspection and maintenance:  Fans should be checked for proper operation and filters checked and/or replaced on a schedule that suits local conditions.  Power wiring connections should be checked and re-torqued every six months.
  • Page 20 Maintenance (cont’d) 460V NEMA 1 NEMA 12 Filter Filter Size Size(s) Size Size(s) A, B 8, 4 A, B 8, 4 A, B 8, 4 A, B 8, 4 Page 20 of 22 Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com...
  • Page 21 Fuses panel has labels, located on the inside of the hinged door, which FRENIC-EcoPAK list the correct size and type of fuses to be used for that panel. In the event that these labels are damaged or missing, please refer to the tables below for replacement fuse...
  • Page 22: Troubleshooting

    TROUBLESHOOTING Drive For drive-specific issues, refer to the drive instruction manual (INR-SI47- FRENIC-Eco 1225-E). Motor Rotation  Problem: Motor turns incorrect direction. Solution: Swap two of the three motor output connections. Page 22 of 22 Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com...