Summary of Contents for Fuji Electric FRENIC-EcoPAK
Page 1
Instruction Manual Non-Bypass Panels FRENIC-EcoPAK Fuji Electric Corp. of America FECA-IN-106 / 122010 Information subject to change without notice. Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com...
Safety Precautions Read this manual thoroughly before proceeding with installation, connections (wiring), or maintenance and inspection. Ensure you have sound knowledge of the device and familiarize yourself with all safety information and precautions before proceeding to operate the drive. Refer to the drive instruction manual (INR-SI47-1225-E) FRENIC-Eco for further safety information.
Page 3
FRENIC-EcoPAK Non-Bypass Panel Overview non-bypass panel is a packaged drive solution in a Type 1 FRENIC-EcoPAK enclosure. NEMA 12 ventilated enclosure is available as an option. Features Type 1 enclosure with “space-saving” footprint Metallic enclosures to reduce radio frequency interference (RFI) ...
Panel Identification Each panel has a nameplate label, like the example pictured above, FRENIC-EcoPAK which contains important information about the panel. This label is located on the inside of the hinged door on the enclosure. CAUTION Refer to the nameplate label to determine the panel input voltage and current requirements prior to installation and wiring.
Installation CAUTION panel should be located indoors: FRENIC-EcoPAK Away from flammable or combustible liquids, gases, and other materials Away from sources of dust, metal shavings, or other particulate material Away from liquids, spray, or mist Away from sources of heat ...
Wiring Overview panel must be connected to an input power source, a motor FRENIC-EcoPAK (output power), and control signals. WARNING Wiring should be performed by a qualified electrician using standard practices as specified by local and national codes. ...
All control wiring, except the damper control output and the programmable relay outputs, connects to the terminals on the drive. The following diagram shows control connections that are available on panels: FRENIC-EcoPAK Description of Control Connections Damper Control output (DMPRLY):...
Page 13
BASIC PANEL STARTUP CAUTION Make sure all power and control wiring is completed before proceeding. As with all electrical equipment installations, insure all safety/wiring instructions have been followed in accordance with this product’s manuals and local and national codes.
Page 14
(INR-SI47-1225-E) for more information. panel was intended to be integrated into a building automation FRENIC-EcoPAK system and controlled by remote signals. If these signals are not available, the panel can be set up to be operated locally. Follow these steps to set the panel up for local operation: 1.
COMMON PARAMETER SETTINGS Also refer to the drive instruction manual (INR-SI47-1225-E) for more FRENIC-Eco information. Factory-set drive parameters and settings These parameters and settings are pre-set from the factory for the panel to be operational. If, for some reason, the drive parameters are reinitialized, these parameters must be reset for correct panel operation.
Page 16
Programming the Drive FRENIC-Eco Also refer to Chapter 3 in the drive instruction manual (INR-SI47-1225-E) FRENIC-Eco for more information. Page 16 of 22 Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com...
Page 17
Programming the Drive FRENIC-Eco (cont’d) To set drive parameters using the keypad, first make sure the drive is stopped. Parameters cannot be changed while the drive is running. To enter the programming menu, press the Program Key (PRG) on the keypad. To return to the previous screen, press either (PRG) or (RESET).
OPERATION Operator Controls panel includes the following controls for local operation and FRENIC-EcoPAK monitoring: Main power disconnect Drive keypad panel includes the following controls for remote operation and FRENIC-EcoPAK monitoring: Analog speed reference input Analog monitor output ...
MAINTENANCE Periodic Maintenance The following items require periodic inspection and maintenance: Fans should be checked for proper operation and filters checked and/or replaced on a schedule that suits local conditions. Power wiring connections should be checked and re-torqued every six months.
Page 20
Maintenance (cont’d) 460V NEMA 1 NEMA 12 Filter Filter Size Size(s) Size Size(s) A, B 8, 4 A, B 8, 4 A, B 8, 4 A, B 8, 4 Page 20 of 22 Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com...
Page 21
Fuses panel has labels, located on the inside of the hinged door, which FRENIC-EcoPAK list the correct size and type of fuses to be used for that panel. In the event that these labels are damaged or missing, please refer to the tables below for replacement fuse...
TROUBLESHOOTING Drive For drive-specific issues, refer to the drive instruction manual (INR-SI47- FRENIC-Eco 1225-E). Motor Rotation Problem: Motor turns incorrect direction. Solution: Swap two of the three motor output connections. Page 22 of 22 Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com...