J505
External PID Control 1 (Display unit)
J505, J605 or J655 selects a display unit for external PID control 1, 2 or 3, respectively.
Under external PID control, the external PID command setting value (SV), feedback value
(PV), manipulated value (MV) and others can be monitored on the keypad. For these values,
select the display units.
For the setting procedure of the monitor display, refer to Chapter 5, Section 5.5.1
"Monitoring the running status."
When external PID control is to be performed with the same unit and scale as for
feedback values, the J505/J605/J655 settings need not be changed. (Factory default:
In accordance with the unit and scale used for feedback values)
Configure the J505/J605/J655 to use different unit and scale from feedback values.
- Data setting range: 0 (Inherit) to 80
Data for
J505/J605/
Display unit
J655
0: Inherit
(Factory default)*
1
No unit
2
%
4
r/min
7
kW
3
20
m
/s (flowrate)
3
21
m
/min (flowrate)
3
22
m
/h (flowrate)
* In accordance with the unit and scale used for feedback values
 For feedback value selection, see function codes E61 to E63.
 The table below lists function codes to be used for setting a unit and scale for feedback
values.
Terminal [12]
Terminal [C1]
Terminal [V2]
J605 (External PID Control 2 (Display unit))
J655 (External PID Control 3 (Display unit))
Data for
J505/J605/
Display unit
J655
24
L/min (flowrate)
25
L/h (flowrate)
40
Pa (pressure)
41
kPa (pressure)
42
MPa (pressure)
43
mbar (pressure)
44
bar (pressure)
45
mmHg (pressure)
Display unit
Maximum scale
C58
C64
C70
6-227
6.3 Details of Function Codes
Data for
J505/J605/
Display unit
J655
46
Psi (pressure)
47
mWG (pressure)
48
inWG (pressure)
60
K (temperature)
61
°C (temperature)
62
°F (temperature)
80
ppm (density)
Minimum scale
C59
C60
C65
C66
C71
C72