o codes: Option Functions
Code
Name
o01
Terminal [Y6A/B/C] Function
(Relay output)
o02
Terminal [Y7A/B/C] Function
o03
Terminal [Y8A/B/C] Function
o04
Terminal [Y9A/B/C] Function
o05
Terminal [Y10A/B/C] Function
o06
Terminal [Y11A/B/C] Function
o07
Terminal [Y12A/B/C] Function
o09
Pt Channel
(Display unit) Temperature
o10
Pt Channel 1
(Sensor type) 0: Jpt100
o11
(Extended functions) 0: No extended function assigned
o12
o15
Pt Channel 2
(Sensor type) Same as o10.
o16
(Extended functions) Same as o11.
o17
o27
Communications Error Processing
o28
o30
Bus configuration parameter 01
o31
Bus configuration parameter 02
o32
Bus configuration parameter 03
o33
Bus configuration parameter 04
o34
Bus configuration parameter 05
o35
Bus configuration parameter 06
o36
Bus configuration parameter 07
o37
Bus configuration parameter 08
o38
Bus configuration parameter 09
o39
Bus configuration parameter 10
o40
Function Code Assignment 1 for Write
Data setting range
Same as E20.
60: K
61: °C
62: °F
1: Pt100
2 : Ni100
3 : Pt1000
4 : Ni1000
5: PID feedback value 1
30: PID feedback value 2
42: External PID feedback value 1
45: External PID feedback value 2
48: External PID feedback value 3
(Filter) 0.0 to 100.0 s
(Filter) Same as o12.
0: Immediately trip with alarm Er5
1: Run for the period specified by timer o28 and then trip with
alarm Er5
2: Retry during the period specified by timer o28. If the retry fails,
immediately trip with alarm Er5.
3: Continue to run. After recovery from the error, run according
to communications command
4 to 9: Same as o27 = 0.
10: Decelerate to a stop and trip with alarm Er5
11: Run for the period specified by timer o28, decelerate to a
stop, and then trip with alarm Er5
12: Retry during the period specified by timer o28. If the retry fails,
decelerate to a stop. If it succeeds, continue to run according
to communications command
13 to 15: Same as when o27 = 3.
(Timer) 0.0 to 60.0 s
0 to 255
Functions of o30 to o39 differ depending upon the bus option
type. For details, refer to the instruction manual of each bus
option.
Same as o30.
0, 1 to 65535
0: No assignment
Data mapped I/O (write)
Whether or not to support the I/O or the number of supports differs
depending upon the bus option type. For the data configuration
procedure, refer to the instruction manual of each bus option.
6-35
6.2 Function Code Tables
Change
Data
Default
Related
when
copying
setting
page
running
N
Y
10
-
N
Y
6
N
Y
25
N
Y
26
N
Y
28
N
Y
36
N
Y
37
Y
Y
61
Y
Y
0
N
Y
0
Y
Y
1.0
N
Y
0
N
Y
0
Y
Y
1.0
Y
Y
0
Y
Y
0.0
N
Y
0
N
Y
0
N
Y
0
N
Y
0
N
Y
0
N
Y
0
N
Y
0
N
Y
0
N
Y
0
N
Y
0
N
Y
0