Fuji Electric FRENIC-HVAC User Manual page 442

Frenic-hvac series
Hide thumbs Also See for FRENIC-HVAC:
Table of Contents

Advertisement

C58
Analog Input Adjustment for Terminal [12] (Display unit)
C58 specifies the display unit for analog input monitor, PID control commands and feedback
amounts on terminal [12].
The specified display unit appears when analog input monitor, SV and PV are displayed on
the main or sub monitor.
Data for
Display unit
C58
1
No display unit
2
%
4
r/min
7
kW
3
20
m
/s (Flowrate)
3
21
m
/min (Flowrate)
3
22
m
/h (Flowrate)
23
L/s (Flowrate)
Setting up an analog input monitor for terminal [12]
1) Input monitor
Set E61 (Terminal [12] extended function) to "20."
2) Display section
Set any of K10 (Main monitor display), K16 (Sub monitor 1 display) and K17 (Sub
monitor 2 display) to "27" (Analog input monitor).
For details, refer to Chapter 5, Section 5.5.1 "Monitoring the running status."
3) Display unit
Select the desired display unit with C58.
4) Scale
- Maximum scale (C59): Set a physical quantity to be displayed when the analog input
value is 100%.
- Minimum scale (C60): Set a physical quantity to be displayed when the analog input
value is 0%.
C59, C60
Analog Input Adjustment for Terminal [12] (Maximum scale, Minimum scale)
C59 and C60 specify the maximum and minimum scales to display easy-to-understand
physical quantity converted from analog input on terminal [12].
- Data setting range: -999.00 to 0.00 to 9990.00 for maximum and minimum scales
Data for
Display unit
C58
24
L/min (Flowrate)
25
L/h (Flowrate)
40
Pa (Pressure)
41
kPa (Pressure)
42
MPa (Pressure)
43
mbar (Pressure)
44
bar (Pressure)
45
mmHg (Pressure)
6-132
Data for
Display unit
C58
46
Psi (Pressure)
47
mWG (Pressure)
48
inWG (Pressure)
60
K (Temperature)
61
°C (Temperature)
62
°F (Temperature)
80
ppm (Density)

Hide quick links: