Fuji Electric FRENIC-HVAC User Manual page 483

Frenic-hvac series
Hide thumbs Also See for FRENIC-HVAC:
Table of Contents

Advertisement

To set data of function code H98, assign the setting of each function to each bit and then
convert the 8-bit binary to the decimal number.
Refer to the assignment of each function to each bit and a conversion example below.
Bit
Function
Lower the carrier
0
frequency automatically
1
Detect input phase loss
2
Detect output phase loss
Select life judgment
3
threshold of DC link bus
capacitor
Judge the life of DC link
4
bus capacitor
DC fan lock detection
(Available for UL open
type-rated inverters of 150
HP or above, NEMA/UL
5
TYPE 1-rated ones of 60
HP or above, andNEMA/
UL TYPE 12-rated ones
of 15 HP or above)
6
--
Switch NEMA/UL
7
TYPE 1/ TYPE 12
enclosure
Data setting range
NEMA/UL
0: Disable
1: Enable
1: Enable
0: Continue to run
1: Enter alarm
1: Enter alarm
processing
processing
0: Continue to run
0: Continue to
1: Enter alarm
run
processing
0: Factory default
0: Factory
1: User-defined setting
default
0: Disable
1: Enable
1: Enable
0: Enable
0: Enable
1: Disable
--
--
0: NEMA/UL
0: NEMA/UL
TYPE 1
1: NEMA/UL
TYPE 12
6-173
6.3 Details of Function Codes
Factory default
NEMA/UL
TYPE1
TYPE12
1: Enable
1: Enter alarm
processing
0: Continue to
run
0: Factory default
1: Enable
0: Enable
--
1: NEMA/UL
TYPE 1
TYPE 12