Advertisement

5) Calibrating the [FM1] / [FM2] output
Calibrate the full scale of the analog meter connected to the terminals [FM1] and [FM2],
using the reference voltage equivalent to +10 VDC or current equivalent to 20 mA. To
output the reference voltage, it is necessary to select the analog output test with the function
code (F31/F35 = 14).
6) Clearing the alarm history
Clear the alarm history saved during the system setup with the function code (H97 = 1).
Depending upon the situation of the practical operation, it may become necessary to modify
the settings of the torque boost (F09) and acceleration/deceleration times (F07/F08).
Confirm the function code data and modify them properly.
The inverter is available in either remote or local mode.
• Remote mode: The inverter is driven by terminal commands, via the communications link
• Local mode:
For details, refer to Section 5.5.4 "Remote and local modes."
or from the keypad which are selectable with function codes.
The inverter is separated from the system and driven by keypad operation.
This mode is convenient for test-run and maintenance.