Fuji Electric FRENIC-HVAC User Manual page 664

Frenic-hvac series
Hide thumbs Also See for FRENIC-HVAC:
Table of Contents

Advertisement

[ 9 ] The motor does not run as expected.
Possible Causes
(1) Incorrect setting of function
code data.
(2) The forced operation function
is in use.
What to Check and Suggested Measures
Check that function codes are correctly configured and no unnecessary
configuration has been done.
 Configure all the function codes correctly.
Make a note of function code data currently configured and then
initialize all function code data using H03.
 After the above process, reconfigure function codes one by one,
checking the running status of the motor.
Check whether the set function code is correct, or whether an
unnecessary setting has been specified.
 Check the forced operation selection (H116) setting.
 Check the digital input terminal forced operation command FMS.
9-30