Fuji Electric FRENIC-HVAC User Manual page 52

Frenic-hvac series
Hide thumbs Also See for FRENIC-HVAC:
Table of Contents

Advertisement

Digital Input Terminals
Symbol
Name
[X1]
Digital input 1
[X2]
Digital input 2
[X3]
Digital input 3
[X4]
Digital input 4
[X5]
Digital input 5
[X6]
Digital input 6
[X7]
Digital input 7
[FWD]
Run forward
command
[REV]
Run reverse
command
Functions
(1) Various signals such as "Coast to a stop," "Enable external
alarm trip," and "Select multistep frequency" can be assigned
to terminals [X1] to [X7], [FWD] and [REV] by setting
function codes E01 to E07, E98, and E99. For details, refer to
Chapter 6 "FUNCTION CODES."
(2) Input mode, i.e. SINK/SOURCE, is changeable by using the
slide switch SW1. (Refer to Section 2.3.2 "Setting up the slide
switches.")
(3) Switches the logic value (1/0) for ON/OFF of the terminals
[X1] to [X7], [FWD], or [REV]. If the logic value for ON of
the terminal [X1] is "1" in the normal logic system, for
example, OFF is "1" in the negative logic system and vice
versa.
(Digital input circuit specifications)
<Control circuit>
[PLC]
SINK
SW1
SOURCE
[X1] to [X7],
[FWD], [REV]
[CM]
Figure 2.4 Digital Input Circuit (a)
Item
Operating
ON level
voltage
OFF level
(SINK)
Operating
ON level
voltage
OFF level
(SOURCE)
Operating current at
ON
(Input voltage is at 0 V)
(For [X7])
Allowable leakage current
at OFF
2-19
2.3 Terminal Specifications
+24 VDC
Photocoupler
5.4kΩ
(1.6kΩ for [X7])
Min.
Max.
0 V
2 V
22 V
27 V
22 V
27 V
0 V
2 V
2.5 mA
5 mA
(9.7 mA)
(16 mA)
0.5 mA