< I.Write: I.C.V (Safe Write) >
PRG > 2(Function Code) > 4(Data Copy) > 1(KP→INV I.Write)
Fref
0.00
Hz
STOP
Iout
0.00A
PWR
0.03kW
PRG
0.Quick Setup
1.Start-up
2.Function Code
3.INV Info
4.Alarm Info
5.User Config
/
PRG>2
1.Data Set
2.Data Check
3.Changed Data
4.Data Copy
5.Timer Setup
6.Initialize
/
PRG>2>4
1,KP→INV I.Write
2.INV→KP Read
3.KP→INV Write
4.KP⇔INV Verify
5.KP Data Check
/
PRG>2>4>1
KP1: 22AR1-4
2012/Jun/23
KP2: ---
---
KP3: ---
---
PRG>2>4>1
KP1=22AR1-4
Start?
---%
Return to previous screen
1. Press the
key while the running mode
screen is displayed.
2. Use the
/
Code], and confirm with the
3. Use the
/
Copy], and confirm with the
4. Use the
/
I Write], and confirm with the
5. Use the
/
KP1–KP3, to store the data you wish to write,
and confirm the destination with the
6. Pressing the
key writes from the keypad.
5-51
5.6 Programming Mode
Return to running
keys to select [2. Function
key.
keys to select [4. Data
key.
keys to select [1. KP→INV
key.
keys to select the location,
key.