Fuji Electric FRENIC-HVAC User Manual page 326

Frenic-hvac series
Hide thumbs Also See for FRENIC-HVAC:
Table of Contents

Advertisement

Code
Name
J105 PID Control 1
J106
(Maximum scale) -999.00 to 0.00 to 9990.00
J107
(Minimum scale) -999.00 to 0.00 to 9990.00
J108
J109
(Tuning manipulated value) 10 to 100% (Maximum frequency = 100%)
J110
J111
J112
D (Differential time) 0.00 to 600.00 s
J113
(Feedback filter) 0.0 to 900.0 s
J114
(Anti-reset wind-up) OFF: Disable
J118
(Upper limit of PID process output) Inherit: Depends on setting of F15
J119
(Lower limit of PID process output) Inherit: Depends on setting of F16
J121
(Alarm output selection) 0: Absolute-value alarm
J122
(Upper level alarm (AH)) OFF: Disable
J124
(Lower level alarm (AL)) OFF: Disable
J127
(Feedback failure detection
(Mode selection))
*6 The upper and lower level values are restricted by the maximum and minimum scales.
(Display unit) 0: Based on the unit/scale of the PID control 1 feedback amount
1: none
2: %
4: r/min
7: kW
Flowrate
3
20: m
/s
3
21: m
/min
3
22: m
/h
23: L/s
24: L/min
25: L/h
Pressure
40: Pa
41: kPa
42: MPa
43: mbar
44: bar
45: mmHg
46: psi (Pound per square inch)
47: mWG
48: inWG
Temperature
60: K
61: °C
62: °F
Density
80: ppm
(Tuning) 0: Disable
1: Short-time response
2: Long-time response
P (Gain) 0.000 to 30.000 times
I (Integral time) 0.0 to 3600.0 s
0.01 to 9990.00
*6
0.0 to 120.0 Hz
0.0 to 120.0 Hz
1: Absolute-value alarm (with Hold)
2: Absolute-value alarm (with Latch)
3: Absolute-value alarm (with Hold and Latch)
4: Deviation alarm
5: Deviation alarm (with Hold)
6: Deviation alarm (with Latch)
7: Deviation alarm (with Hold and Latch)
-999.00 to 0.00 to 9990.00
-999.00 to 0.00 to 9990.00
0: Disable (Turns ON output signals (PV1-OFF) and continues
operation.)
1: Enable (Free run stop (PV1 trip))
2: Enable (Deceleration and stop (PV1 trip))
3: Enable (Continuation of operation at the maximum frequency
(upper limit frequency))
4: Enable (Continuation of operation at the minimum frequency
(lower limit frequency))
5: Enable (Continuation of operation at the frequency used when
failure is detected.)
6: Enable (Shift to PID control 2 (PID control 1 is restored when
failure is recovered from.))
Data setting range
*6
*6
6-16
Change
Data
Default
Related
when
copying
setting
page
running
N
Y
0
6-190
N
Y
100
6-191
N
Y
0.00
Y
Y
0
6-192
Y
Y
10%
Y
Y
0.100
6-194
Y
Y
0.0
Y
Y
0.00
Y
Y
0.5
Y
Y
OFF
6-197
Y
Y
Inherit
6-198
Y
Y
Inherit
Y
Y
0
Y
Y
OFF
Y
Y
OFF
Y
Y
0
6-201