Initialize U code data (H03 = 12)
Initializes the customizable logic (U code) data. Any other function code data are not
initialized.
Initialize according to application (H03 = 71, 72, 73)
H03 initializes data of the specified function codes to the values required for application such
as drive control and control objects. Function codes for quick setup also change according to
application.
This application-specific initialization is convenient for pump control.
H03 initializes data of function codes not listed below will be initialized to the factory
defaults.
When H03 = 71 (Initialize according to application (Compressor ))
Object function codes
F02: Operation Method
F14: Restart Mode after Momentary
Power Failure (Mode selection)
F15: Frequency Limiter (High)
F16: Frequency Limiter (Low)
F26: Motor Sound (Carrier frequency)
F35: Pulse Output [FM2] (Function)
F42: Drive Control Selection 1
E06: Terminal [X6] Function
E07: Terminal [X7] Function
E62: Terminal [C1] Extended Function
E63: Terminal [V2] Extended Function
C64: Analog Input Adjustment for
Terminal [C1] (Display unit)
C65: Analog Input Adjustment for
Terminal [C1] (Maximum scale)
H09: Starting Mode (Auto search)
H91: Current Input Wire Break Detection
J101: PID Control 1 (Mode selection)
J110: PID Control 1 P (Gain)
J111: PID Control 1 I (Integral time)
K10: Main Monitor (Display item
selection)
K16: Sub Monitor 1 (Display item
selection)
K17: Sub Monitor 2 (Display item
selection)
K91: Shortcut Key Function for
Running Mode (Jump-to screen)
K92: Shortcut Key Function for
Running Mode (Jump-to screen)
1: External signals (Terminal command FWD
or REV)
3: Continue to run, for heavy inertia or general
loads
50.0 Hz
25.0 Hz
3 kHz
2: Output current
1: Dynamic torque vector control
171: PID multistep command 1 (PID-SS1)
172: PID multistep command 2 (PID-SS2)
5: PID feedback value 1
32: Auxiliary input 2 to PID process command
44: bar
10.00
2: Enable (At restart after momentary power
failure and at normal start)
0.5 s
1: Enable (Process control, normal operation)
2.500 times
0.2 s
51: PID feedback amount (final) in physical
quantity
50: PID command (final) in physical quantity
1: Output frequency 1 (before slip
compensation)
in
61: Tools - PID Monitor (PID monitor)
in
32: INV Infor - Op Monitor (Operation monitor)
6-142