F07, F08
Acceleration Time 1, Deceleration Time 1
F07 specifies the acceleration time, the length of time the frequency increases from 0 Hz to
the maximum frequency. F08 specifies the deceleration time, the length of time the frequency
decreases from the maximum frequency down to 0 Hz.
- Data setting range: 0.00 to 3600.00 (s)
Acceleration/deceleration time
Acceleration/
deceleration time
Acceleration/
deceleration time 1
Acceleration/
deceleration time 2
Acceleration/
deceleration time 3
Acceleration/
deceleration time 4
Force to stop
Acceleration/Deceleration pattern (H07)
H07 specifies the acceleration and deceleration patterns (patterns to control output
frequency).
Data
Acceleration/
for
deceleration
H07
pattern
Linear
0
S-curve
(Weak)
1
S-curve
(Strong)
2
Curvilinear
3
E10, E12, E14 (Acceleration Time 2, 3 and 4)
E11, E13, E15 (Deceleration Time 2, 3 and 4)
Function code
Switching factor of acceleration/deceleration time
ACC
DEC
( Refer to the descriptions of E01 to E07.)
time
time
RT2
RT1
F07
F08
OFF
OFF
E10
E11
OFF
ON
E12
E13
ON
OFF
E14
E15
ON
ON
If terminal command STOP (data = 30) is turned OFF, the
inverter decelerates to a stop with the deceleration time
-
H56
specified by H56. After that, the inverter displays alarm Er6
and enters an alarm state.
The inverter runs the motor with the constant acceleration and
deceleration.
To reduce an impact that
acceleration/deceleration
would make on the machine,
the inverter gradually
accelerates or decelerates the
motor in both the starting
and ending zones of
acceleration or deceleration.
Acceleration/deceleration is linear below the base frequency
(constant torque) but it slows down above the base frequency to
maintain a certain level of load factor (constant output).
This acceleration/deceleration pattern allows the motor to accelerate
or decelerate with the maximum performance of the motor.
6-53
6.3 Details of Function Codes
H07 (Acceleration/Deceleration Pattern)
H56 (Deceleration Time for Forced Stop)
The combinations of ON/OFF states of
the two terminal commands RT2 and
RT1 offer four choices of acceleration/
deceleration time 1 to 4. (Data = 4, 5)
If no terminal command is assigned,
only the acceleration/deceleration time 1
(F07/F08) is effective.
Motion
Weak:
The acceleration/deceleration rate to
be applied to all of the four
inflection zones is fixed at 5% of the
maximum frequency.
Strong:
The acceleration/deceleration rate to
be applied to all of the four
inflection zones is fixed at 10% of
the maximum frequency.
Function