Function code settings
Function
Function
code
y98
Select run/frequency
command sources
The table below lists the error processing to apply when a timeout occurs.
Function code
o27
o28
0, 4 to 9
--
1
0.0 to 60.0s
2
0.0 to 60.0s
3, 13 to
--
15
10
--
11
0.0 to 60.0s
12
0.0 to 60.0s
Factory
Function code
default
data to be set
0
Descriptions
Immediately coast to a stop and trip with Er5.
After the time specified by o28, coast to a stop and
trip with Er5.
If the communications link is restored within the time
specified by o28, ignore the communications error. If
a timeout occurs, coast to a stop and trip with Er5.
Keep the current operation, ignoring the
communications error. (No Er5 trip occurs.)
Immediately decelerate to a stop. After stop, trip with
Er5.
After the time specified by o28, decelerate to a stop.
After stop, trip with Er5.
If the communications link is restored within the time
specified by o28, ignore the communications error. If
a timeout occurs, decelerate to a stop. After stop, trip
with Er5.
4-78
Description
Freq. command Run command
3
0:
Inverter
1:
Ethernet
2:
Inverter
3:
Ethernet
Inverter
Inverter
Ethernet
Ethernet
Remarks
Specify the
deceleration time
with the inverter's
function code F08.
Same as above.
Same as above.