9.4.2

Problems with inverter settings

[ 1 ] Nothing appears on the LCD monitor.
Possible Causes
(1) No power (neither main power
nor auxiliary control power)
supplied to the inverter.
(2) The keypad was not properly
connected to the inverter.
[ 2 ] Connecting... display
Problem The "Connecting..." display does not change.
Possible Causes
(1) The keypad is poorly connected. Check the remote operation extension cable conductance.
[ 3 ] "This inverter is not supported." display
Problem "This inverter is not supported." is displayed and the keypad turns ON and OFF repeatedly.
Possible Causes
(1) The keypad and inverter are not
compatible.
[ 4 ] "USB Connected." display
Problem "USB Connected." is displayed and operation is not possible.
Possible Causes
(1) A USB cable is connected to the
inverter.
What to Check and Suggested Measures
Check the input voltage and interphase voltage unbalance.
 Turn ON a molded case circuit breaker (MCCB), a residual-current-
operated protective device (RCD)/earth leakage circuit breaker
(ELCB) (with overcurrent protection) or a magnetic contactor
(MC).
 Check for voltage drop, phase loss, poor connections, or poor
contacts and fix them if necessary.
Check whether the keypad is properly connected to the inverter.
 Remove the keypad, put it back, and see whether the problem
recurs.
 Replace the keypad with another one and check whether the
problem recurs.
When running the inverter remotely, ensure that the extension cable is
securely connected both to the keypad and to the inverter.
 Disconnect the cable, reconnect it, and see whether the problem
recurs.
 Replace the keypad with another one and check whether the
problem per recurs.
What to Check and Suggested Measures
 Replace the remote operation extension cable conductance.
What to Check and Suggested Measures
Check the keypad and inverter compatibility.
 Connect a keypad that is compatible with the inverter.
What to Check and Suggested Measures
The inverter has been set to USB communication mode by connecting it
to the computer via a USB cable.
 If not necessary to connect to the computer, disconnect the USB
cable.
9-31