Table 11.1 Recommended Wire Sizes (continued)
Inverter type
1
FRN001AR1-5U
2
FRN002AR1-5U
3
FRN003AR1-5U
5
FRN005AR1-5U
7.5 FRN007AR1-5U
10
FRN010AR1-5U
15
FRN015AR1-5U
20
FRN020AR1-5U
25
FRN025AR1-5U
30
FRN030AR1-5U
40
FRN040AR1-5U
50
FRN050AR1-5U
60
FRN060AR1-5U
75
FRN075AR1-5U
100
FRN100AR1-5U
125
FRN125AR1-5U
150
FRN150AR1-5U
200
FRN200AR1S-5U
250
FRN250AR1S-5U
300
FRN300AR1S-5U
*1 The recommended wire size for main circuits is for the 70°C (158°F) 600 V PVC wires used at an
ambient temperature of 40°C(104°F).
Note: A box () replaces an alphabetic letter depending on the enclosure.
M (NEMA/UL TYPE 1) or L (NEMA/UL TYPE 12)
10. The inverter has been tested with IEC/EN 61800-5-1 Short-circuit Test under the following
conditions.
Short-circuit current in the supply: 10,000 A
240V or below (200V class series inverters of 18.5 kW (25HP) or below.)
230V or below (230V class series inverters of 22 kW (30HP) or above.)
480V or below (480V class series inverters)
600V or below (575V class series inverters)
Recommended wire size (mm
Main terminal
Main power input
Inverter
outputs
[L1/R, L2/S,
Inverter's
[U, V, W]
L3/T]
grounding
1
1
*
[ G] *
2.5
10
4
6
10
25
25
35
35
70
70
95
120
95
150
185
11-7
11.1 欧州規格の適合について
2
)
DC reactor
Control
[P1, P(+)]
circuit
1
*
1
*
2.5
4
6
DCR
built-in
10
0.75
16
25
35
50
70
95
120
150
185
240
Aux.
Aux.
main
control
circuit
power
power
supply
supply
[R0, T0]
[R1, T1]
-
2.5
2.5
11