J516
External PID Control 1 (Proportional operation output convergent value)
J616 (External PID Control 2 (Proportional operation output convergent value))
J666 (External PID Control 3 (Proportional operation output convergent value))
Exclusively for external PID control, this setting value can be added to the external PID
output. J516/J616/J666 sets external PID controls 1/2/3 respectively.
- Data setting range: 1 to 150 (%)
Also, by disabling I (integral time) and D (differential time) to enable only P (gain) and this
value, the following comparison is possible.
● Normal operation
Manipulated value
(MV)
ON
100%
J516
0%
Command value (SV)
PID control
%/EPID1
Manual
command
J518
selection
Upper
limiter
PID
+
processor
+
External PID control 1
Lower
(ON/OFF control hysteresis width)
limiter
J516
J519
● Reverse operation
Manipulated value
(MV)
100%
P gain
OFF
0%
Feedback value (PV)
6-235
6.3 Details of Function Codes
External PID
control (mode
selection)
OFF
External PID 1
output
ON
P gain
J516
OFF
Feedback value (PV)
Command value (SV)