Fuji Electric FRENIC-HVAC User Manual page 335

Frenic-hvac series
Hide thumbs Also See for FRENIC-HVAC:
Table of Contents

Advertisement

d codes: Application Functions 2
Code
Name
d51
Reserved *5
d55
Reserved *5
d69
Reserved *5
d98
Reserved *5
d99
Reserved *5
*5 These function codes are reserved for particular manufacturers. Unless otherwise specified, do not access these function codes.
*8 "5" for inverters of 5 HP or below, "10" for those of 7.5 to 30 HP, "20" for those of 40 HP or above.
U codes: Customizable Logic Function
Code
Name
(Mode selection) 0: Disable
U00
Customizable Logic
U01
Customizable Logic: Step 1
(Control function)
U02
U03
Available in the ROM version 1600 or later.
*10 Available at ROM version
2450
or later.
Data setting range
0 to 500
0000H to 00FFH
30.0 to 100.0 Hz
0000H to FFFFH
0 to 3
Data setting range
1: Enable (Customizable logic operation)
Changing this code data from "1" to "0" causes an ECL alarm.
0:
No function assigned
10: Through output + General-purpose timer
20: ANDing + General-purpose timer
30: ORing + General-purpose timer
40: XORing + General-purpose timer
50: Set priority flip-flop + General-purpose timer
60: Reset priority flip-flop + General-purpose timer
70: Rising edge detector + General-purpose timer
80: Falling edge detector + General-purpose timer
90: Rising & falling edges detector + General-purpose timer
100: Hold + General-purpose timer
110: Increment counter
120: Decrement counter
130: Timer with reset input
2001-3002: Analog input
4001-5114: Analog + digital
(Input 1) 0 (1000):
Inverter running
1 (1001):
Frequency (speed) arrival signal
2 (1002):
Frequency (speed) detected
3 (1003):
Undervoltage detected (Inverter stopped)
5 (1005):
Inverter output limiting
6 (1006):
Auto-restarting after momentary power
failure
7 (1007):
Motor overload early warning
10 (1010): Inverter ready to run
11:
Switch motor drive source between
commercial power and inverter output
(For MC on commercial line)
12:
Switch motor drive source between
commercial power and inverter output
(For secondary side)
13:
Switch motor drive source between
commercial power and inverter output
(For primary side)
15 (1015): Select AX terminal function
(For MC on primary side)
16 (1016): Shifted to pattern operation stage
17 (1017): Pattern operation cycle completed
18 (1018): Pattern operation stage number
19 (1019): Pattern operation stage number
20 (1020): Pattern operation stage number
22 (1022): Inverter output limiting with delay
25 (1025): Cooling fan in operation
26 (1026): Auto-resetting
28 (1028): Heat sink overheat early warning
30 (1030): Lifetime alarm
33 (1033): Reference loss detected
35 (1035): Inverter output on
36 (1036): Overload prevention control
37 (1037): Current detected
38 (1038): Current detected 2
42 (1042): PID alarm
43 (1043): Under PID control
44 (1044): Motor stopped due to slow
flowrate under PID control
45 (1045): Low output torque detected
52 (1052): Running forward
53 (1053): Running reverse
6-25
6.2 Function Code Tables
Change
Data
Default
when
copying
setting
running
*8
N
Y
N
Y
0
Y
Y
30.0
Y
Y
0
Y
Y
0
Change
Data
Default
when
copying
setting
running
Y
Y
0
N
Y
0
(RUN)
N
Y
100
(FAR)
(FDT)
(LU)
(IOL)
(IPF)
(OL)
(RDY)
(SW88)
(SW52-2)
(SW52-1)
(AX)
(TU)
(TO)
(STG1)
(STG2)
(STG4)
(IOL2)
(FAN)
(TRY)
(OH)
(LIFE)
(REF OFF)
(RUN2)
(OLP)
(ID)
(ID2) *10
(PID-ALM)
(PID-CTL)
(PID-STP)
(U-TL)
(FRUN)
(RRUN)
Related
page
6-249
Related
page
6-249