Fuji Electric FRENIC-HVAC User Manual page 76

Frenic-hvac series
Hide thumbs Also See for FRENIC-HVAC:
Table of Contents

Advertisement

(2) Open type: FRN075AR1S-2U, FRN100AR1S-2U
Carrier frequency
setting (kHz)
0.75 to 2
3
4
5
6
7
8
9
10
(3) Open type: FRN125AR1S-2U
Carrier frequency
setting (kHz)
0.75 to 2
3
4
5
6
(4) Open type: FRN150AR1S-4U to FRN1000AR1S-4U
Carrier frequency
setting (kHz)
0.75 to 2
3
4
5
6
Note: For 460 V class series inverters of 1000 HP, the upper limit of the carrier frequency is 4 kHz.
Output current derating factor (rated current ratio)
Ambient temperature
40°C(104°F)
100%
100%
100%
100%
100%
100%
100%
100%
100%
Output current derating factor (rated current ratio)
Ambient temperature
40°C(104°F)
100%
100%
100%
100%
100%
Output current derating factor (rated current ratio)
Ambient temperature
40°C(104°F)
100%
100%
100%
100%
100%
2-43
2.6 Derating of Rated Output Current
Ambient temperature
50°C(122°F)
100%
100%
100%
100%
100%
95%
90%
85%
80%
Ambient temperature
50°C(122°F)
100%
100%
100%
95%
85%
Ambient temperature
50°C(122°F)
100%
100%
100%
90%
80%

Hide quick links: