Connection Method - Fuji Electric FRENIC-HVAC User Manual

Frenic-hvac series
Hide thumbs Also See for FRENIC-HVAC:
Table of Contents

Advertisement

8.1.3

Connection method

• Up to 31 inverters can be connected to one host equipment.
• The protocol is commonly used in the FRENIC series of general-purpose inverters, so programs for
similar host equipment can run/stop the inverter.
(The parameters specifications may differ depending on the equipment.)
• Fixed-length transmission frames facilitate developing communication control programs for hosts.
For details of RS-485 communication, refer to the RS-485 Communication User's Manual.
Multi-drop connection using the RS-485 communications port 1 (for connecting the keypad)
For connecting inverters in multi-drop connection, use the branch adapters for multi-drop connection
as shown below.
• Pins 1, 2, 7, and 8 on the RJ-45 connector are exclusively assigned to power supply and
grounding for keypads. When connecting other devices to the RJ-45 connector, take care
not to use those pins. Failure to do so may cause a short-circuit hazard. Use pins 4 and 5
only. (For details, refer to Section 8.1.2 "Terminal specifications for RS-485
communication.")
• When selecting additional devices to prevent the damage or malfunction of the control
PCB caused by external noises or eliminate the influence of common mode noises, be sure
to refer to Section 8.1.4 "Communications support devices."
• The maximum wiring length must be 500 m.
• Use cables and converters meeting the specifications for proper connection. (Refer to [2]
"Requirements for the cable (COM port 1: for RJ-45 connector)" in Section 8.1.4
"Communications support devices."
Figure 8.1 Multi-drop Connection (Using the RJ-45 connector)
8-4
FRENIC-HVAC
FRENIC-HVAC
FRENIC-HVAC