Fire Mode (Reference frequency) (H118)
- Data setting range: Inherit, 0.1 to 120.0 (Hz)
Specify speed (reference frequency) at which operation is to be performed when forced
operation (Fire Mode) is enabled.
H118 data
Inherit
The frequency selected through frequency setting 1 (F01) and 2 (C30) is
followed.
0.1 to 120.0
Arbitrary frequencies can be set in 0.1 Hz steps.
Fire Mode (Rotation direction) (H119)
- Data setting range: 0, 2, 3
Set an operation instruction (rotation direction) to be followed when forced operation (Fire
Mode) is enabled.
H119 data
Follows the operation instruction selected through drive operation (F02).
* When the operation instruction is OFF, operation is not performed at the
0
frequency specified with H118 (reference frequency). Note, however, that
the mode at that time is forced operation execution status.
Operation through forward rotation (FWD)
2
* Forward rotation is forcibly performed irrespective of presence and absence
of an operation instruction.
Operation through reverse rotation (REV)
3
* Reverse rotation is forcibly performed irrespective of presence and absence
of an operation instruction.
Fire Mode (Start method) (H120)
- Data setting range: 0, 1
Set the start method to be followed when Fire Mode is enabled.
H120 data
Follows the start methods specified with instant power failure restart (F14) and
0
H09 (starting mode).
STM mode (auto search for idling motor speed to run the idling motor without
1
stopping it)
Fire Mode (Reset interval) (H121)
- Data setting range: 0.5 to 20.0 (s)
Set time delay to auto cancel of trip status for a case where the inverter enters trip status and
stops during forced operation (Fine Mode).
6.3 Details of Function Codes