Relay Output Interface Card (Opc-Ry) - Fuji Electric FRENIC-HVAC User Manual

Frenic-hvac series
Hide thumbs Also See for FRENIC-HVAC:
Table of Contents

Advertisement

4.4.3.2

Relay output interface card (OPC-RY)

The relay output interface card OPC-RY converts general-purpose output signals issued via inverter
terminals [Y1] and [Y2] or [Y3] and [Y4] to a relay output (one transfer contact). It has two
independent transfer contacts so that using two cards allows the user to activate up to four contact
outputs (Y1 to Y4).
A signal to be output to each contact can be defined with function codes E20 to E23. Selecting "Active
OFF" for a contact output with the function code enables the contact to be turned ON without relay coil
excitation. This is useful for a fail-safe application for the power system.
Ports available for the interface card and functionality assignments
A FRENIC-HVAC inverter has three option connection ports. Note that each port has some limitations
as shown below.
Option
connection port
Relay contact output 1
A-port
Relay contact output 2
Relay contact output 1
B-port
Relay contact output 2
C-port
Not available for the relay output interface card
Terminal functions
Symbol
[1A]
[1B]
Relay contact output 1
[1C]
[2A]
[2B]
Relay contact output 2
[2C]
Electrical requirements
Item
Contact capacity
Contact life
Safety Standards/Directives
Output signal
Assignment
Function code E20 (Y1)
Function code E21 (Y2)
Function code E22 (Y3)
Function code E23 (Y4)
Name
Relay contacts to output signals selected by function
codes E20 and E22, such as Inverter Running, Frequency
Arrival and Overload Early Warning.
In "active ON", the contact [1A] – [1C] closes and [1B] –
[1C] opens while the signal is active.
Relay contacts to output signals selected by function
codes E21 and E23, such as Inverter Running, Frequency
Arrival and Overload Early Warning.
In "active ON", the contact [1A] – [1C] closes and [1B] –
[1C] opens while the signal is active.
250 VAC, 0.3A, cosΦ = 0.3, or 48 VDC, 0.5A (resistor load)
200,000 times (ON/OFF every 1 second) at 250 VAC, 0.3A
200,000 times (ON/OFF every 1 second) at 48 VDC, 0.5A
Note: When frequent ON/OFF switching is anticipated (for example,
when using the current limit function with the inverter output limiting
signal), use the terminals [Y1] to [Y4] (transistor outputs) instead.
EN61800-5-1, Overvoltage Category II (Reinforced Insulation) 250
VAC class
4-53
Notes
Do not connect this card to the
inverter's terminal [Y1] or
[Y2].
Do not connect this card to the
inverter's terminal [Y3] or
[Y4].
Descriptions
Specifications