If the connection
destination is:
Select the internal step outputs SO01 to SO14 to be
General-purpose
analog output
connected to the customizable logic output signals 1
(terminal [FM])
CL01 to 7 CL07.
To specify the general-purpose analog output
(terminal [FM]) to be connected to the customizable
logic output signals 1 CL01 to 7 CL07, select CL01
to CL07 on the function selection side of the
general-purpose analog output (terminal [FM]).
For the general-purpose digital output (terminal [Y]), the data is renewed over a
5-ms cycle. To securely output a customizable logic signal via Y terminals, include
on- or off-delay timers in the customizable logic. Otherwise, short ON or OFF
signals may not be reflected on those terminals.
Function
Name
code
U71
Customizable logic output signal 1
(Output selection)
U72
Customizable logic output signal 2
(Output selection)
U73
Customizable logic output signal 3
(Output selection)
U74
Customizable logic output signal 4
(Output selection)
U75
Customizable logic output signal 5
(Output selection)
U76
Customizable logic output signal 6
(output selection)
U77
Customizable logic output signal 7
(output selection)
6.3 Details of Function Codes
Configuration
Data setting range
0: Disable
1: Output of step 1, SO01
2: Output of step 2, SO02
3: Output of step 3, SO03
4: Output of step 4, SO04
5: Output of step 5, SO05
6: Output of step 6, SO06
7: Output of step 7, SO07
8: Output of step 8, SO08
9: Output of step 9, SO09
10: Output of step 10, SO10
11: Output of step 11, SO11
12: Output of step 12, SO12
13: Output of step 13, SO13
14: Output of step 14, SO14
6-263
Function codes
U71 to U77
F31, F35
Default
setting
0
0
0
0
0
0
0