Table 1
Input type code
Parameter :
Group
Input type
RTD
· Pt100 (IEC)
Thermocouple
· J
· K
I
· R
· B
· S
· T
· E
· N
· PL-II
Table 2
Control output action code
Parameter :
Control output action Output at Burn-out*
Code
Output
Output 1
0
Reverse action
1
Single
2
(Control output 1)
Direct action
3
4
5
Reverse action
6
7
8
9
Dual
Direct action
10
11
Control output
12
1 and 2.
13
Heating/Cooling
Reverse action
14
15
16
17
Direct action
18
19
Code
1
2
3
4
5
6
7
8
12
13
Output 2
Output 1
Output 2
Lower limit
Upper limit
---
---
Lower limit
Upper limit
Lower limit
Lower limit
Upper limit
Lower limit
Upper limit
Upper limit
Direct action
Lower limit
Lower limit
Upper limit
Lower limit
Upper limit
Upper limit
Lower limit
Lower limit
Upper limit
Lower limit
Upper limit
Upper limit
Reverse action
Lower limit
Lower limit
Upper limit
Lower limit
Upper limit
Upper limit
– 28 –
Group
Input type
II
1 to 5VDC,
4 to 20mA DC
· In case of 4 to 20mA DC input, mount a 250Ω
resistor enclosed in the package box.
TC
RTD
(within Group I)*
1 to 5 VDC
TC/RTD
4 to 20 mA DC
(Group I)*
(Group II)*
(*) Outputs when Error Indication Group I.
Please refer to 8 (Error indications).
This is effective even in Standby mode.
Lower limit:OFF or 4mA or less
Upper limit:ON or 20mA or more
[Caution for dual output] (option)
(1) Parameter "I" and "D" can not be set
separately.
(2) In case "P"=0 (ON/OFF control) for heating
side, cooling side becomes ON/OFF
control automatically.
(3) In case "Cool" =0.0, cooling side becomes
ON/OFF control. And hysteresis is fixed at
0.5%FS.
Code
16
Can be modified by
changing "P-n2"
Modification
not possible