Section 1 Overview

1-1 Function List

SPF series basic unit has a built-in high-speed counter. The table below lists the main functions.
Function
No. of channels *1
Pulse input format
Count signal
Counting speed *2
Counting range
Multiplication function
Count enable/stop function
External control input
Current value clear function
Current value latch function
Current value preset function
Set value write function
Delay timer function
Special relay / special register
for high-speed counter
* 3
High-speed counter FB
* 4
*1 SPF basic unit has a built-in hardware high-speed counter for eight channels. To use the high-speed counter, set the
channels to be used (CH0 t CH7) and counter mode (pulse input format and input to be used) on the "High-speed counter
setting" screen in the system definition. Since the input to be used differs depending on the basic unit type, the number of
usable channels is determined by the basic unit type and system definition setting.
*2 The counting speed of the high-speed counter is determined by the response speed of the input address to be used. The
input response speed of SPF basic unit differs depending on the basic unit type and input to be used.
For details, refer to "2-2 Input Specifications".
*3 For details, refer to "2-3 Special Relay/Register Specifications."
*4 For details, refer to "3-2 High-speed Counter FB."
NA0Po14o
NA0Po24o
Max. 8 channels
• 90-degree phase-differential two-phase signal
• Forward pulse (A-phase) / Reverse pulse (B-phase)
• Command pulse (A-phase) / Direction signal (B-phase)
Open collector (24V DC)
High-functionality type Basic unit: 200kHz, 20kHz
Standard type Basic unit: 100kHz, 20kHz
Note: When used in "90-degree phase-differential two-phase signal" mode, the counting speed
becomes half.
-2,147,483,648 to 2,147,483,647 (DINT-type)
x1, x2, x3, x4
Count can be stopped from external input or an application.
• Count enable/stop input a Set an arbitrary input on the basic unit.
• Current value clear input a Set an arbitrary input on the basic unit.
• Current value latch input a Set an arbitrary input on the basic unit.
The current value can be cleared to 0 from external input or an application.
The current value can be latched from external input or an application.
The dedicated instruction (W_HSC) is used.
The dedicated instruction (W_HSC) is used.
Max. 8
Channels not used as a high-speed counter can be used as a delay timer (free run counter)
with 0.1ms of base time.
• Count enable/stop flag (Write flag)
• Current value clear flag (Write flag)
• Current value latch status (Read flag)
• Current value latch data (Read flag)
• Count direction signal (Write flag)
• Counter current value (Read flag)
• Counter set value (Write flag)
• High-speed counter match flag (Event task start flag)
The following four types of FBs are provided.
• R_HSC High-speed counter current value direct read FB
• W_HSC High-speed counter current/set value write FB
• W_HSC_FLG High-speed counter flag control FB
• R_HSC_LATCH High-speed counter current value latch FB
NA0Po32o
1-1
NA0Po40o
NA0Po60o