Conditions where self-tuning cannot be used
Self-tuning cannot be used in the following situations:
During control standby
During ON/OFF (2-position) control
During auto-tuning
During ramp soak progress
When there is error input
When set for dual output
When any of the P, I, D, Ar parameters are set to manual
During manual mode
During soft start progress
Conditions to halt self-tuning
Halt self-tuning in the following situations:
When there is a change in SV (This includes the case where SV changes because of the
ramp soak function, remote SV function, or ramp SV.)
When self-tuning has not finished after running for nine or more hours
Setting self-tuning
Turn on power of the controller and set the SV.
1
Display the system menu ("
S S S S Y Y Y Y S S S S [ [ [ [ h h h h 7 7 7 7
2
Display the controller parameter ("
3
Press the
key to set the value.
4
Turn off power of the controller.
5
Turn on power of the control target equipment and the controller. Turn on
6
power of the control equipment first.
Self-tuning will begin.
process value
SV
tuning
dead time
lag time
The equipment will not tune correctly if power of the controller is
Point
turned on first.
To reset self-tuning, set the control method to PID ("
before changing back to self-tuning.
7-5
PID2 Control
In case which the power supply of the control target goes ON → OFF → ON, this PID2 control
can suppress the amount of overshoot.
This control introduces an algorithm to prevent the calculated PID result from becoming a mis-
calculation, even when the control loop is open.
You will need to run auto-tuning to set the PID parameter when using PID2 control.
Features of PID2 Control
process value
control equipment power
control loop
Setting PID2 control
S S S S Y Y Y Y S S S S C C C C h h h h 7 7 7 7
Display the system menu ("
1
Display the control parameter ("
2
Press the
key to set the value.
3
7-6
Auto-tuning
Run auto-tuning to set the PID parameter automatically.
A A A A t t t t
"
" set value
Behavior
Function
"
o o o o F F F F F F F F
"
Stop/Finish
Stops or finishes auto-tuning.
"
o o o o n n n n
"
Normal type
The standard auto-tuning for SV reference. Choose this
auto-tuning in most situations.
L L L L o o o o
"
"
Low PV type
Auto-tuning for SV-10% reference. Choose this when you
want to suppress the overshoot when tuning.
").
[ [ [ [ t t t t r r r r L L L L
") and choose self-tuning ("
t
suppress overshoot
SV
PV
t
ON
OFF
close
close
open
").
C C C C T T T T r r r r L L L L
") and choose PID2 ("
P P P P i i i i d d d d 2 2 2 2
").
Normal type
process value AT start
SV
Point
Running auto-tuning
Display the operation menu ("
1
Display auto-tuning ("
2
Choose the standard type ("
Press the
3
A decimal point will blink at the bottom of the display during auto-tuning.
When auto-tuning has successfully competed, blinking decimal point will turn off and
overwrites the PID.
S S S S E E E E L L L L F F F F
").
Point
P P P P i i i i D D D D
") once
7-7
Valve controls adjust and control the valve position according to [OPEN] and [CLOSE] of the
contact signal.
Turn on the contact outputs in manual mode, so that pressing the
pressing the
Note: Srv2 or PFb cannot be used in PXG4.
Setting Servo Control 1
Display the system menu ("
1
Display the control parameter ("
2
This chooses "Servo Control 1".
Press the
3
Point
Caution
Setting the valve stroke time
The valve stroke time must be set to use valve control.
Display the PFB menu ("
1
Display the valve stroke time parameter ("
2
valve in use.
Press the
3
– 11 –
Low PV type
process value AT start
AT calculating
PID control
PV
t
Set the following parameters before running auto-tuning.
PV input type / PV input upper limit / PV input lower limit / Decimal
position / PV input filter in the setup channel menu ("
OUT1 proportion cycle (OUT2 proportion cycle) in the PID channel
menu ("
P P P P i i i i d d d d C C C C h h h h 2 2 2 2
").
o o o o P P P P E E E E [ [ [ [ h h h h 1 1 1 1
").
A A A A t t t t
") and choose the tuning type.
o o o o n n n n
") or low PV type ("
key to start auto-tuning.
PID parameter which is set after auto tuning has finished normally
will be maintained even when the power is turned off. However, the
PID value will not be changed if the power is turned off during auto-
tuning. In this case, rerun auto-tuning.
The equipment will use ON/OFF (2 position) control during auto-
tuning, so there may be a large change in PV according to the pro-
cess. Do not use auto-tuning for processes that do not permit a
large change in PV. Do not use auto-tuning for processes such as
pressure control and flow control that have a fast response.
Auto-tuning is not behaving normally if it has not finished after four
or more hours have passed. In these cases, recheck parameters
such as input/output wiring, control output behavior (normal/
reverse), and input sensor type.
Rerun auto-tuning if there is a large change in SV, a change in the
PV input type, or a change in the control target conditions that
reduces the effectiveness of the controls.
You can run auto-tuning when the control type is set to "fuzzy" or
"PID2".
You cannot run auto-tuning in manual mode.
When using the PID selection function, the auto-tuning result for
the selected PID group is stored.
Auto tuning is forcibly terminated when SV changes because of the
ramp soak function, remote SV function, or ramp SV.
Valve Control (Servo Control 1)
key means "CLOSE"
OPEN contact output
CLOSE contact output
Valve motor
(servo 1)
Valve
S S S S Y Y Y Y S S S S C C C C h h h h 7 7 7 7
").
P P P P r r r r C C C C S S S S
") and choose servo control 1 ("
key to set the value.
An interlock function is not built in.
Chattering may occur if the dead band ("
is set too small.
P P P P F F F F B B B B [ [ [ [ h h h h 1 1 1 1 0 0 0 0
").
key to set the value.
AT calculating
SV-10%FS
SV
PV
PID control
t
S S S S E E E E T T T T C C C C h h h h 6 6 6 6
")
L L L L o o o o
") according to the control target.
key means "OPEN", and
set value input
(temperature)
boiler
S S S S r r r r v v v v 1 1 1 1
").
P P P P G G G G A A A A P P P P
P P P P F F F F B B B B C C C C h h h h 1 1 1 1 0 0 0 0
") in the PFB menu ("
t t t t r r r r v v v v L L L L
") and set the stroke time for the
")

Advertisement

loading