11 MANUAL CONTROL

11.2 JOG operation

11.2.1 Outline of JOG operation

Cd. 19 JOG speed
Acceleration for the acceleration
time selected in Pr. 33
PLC READY signal
AD75 READY signal
Forward run JOG start signal
[Y16, Y18, Y1A]
Reverse run JOG start signal
[Y17, Y19, Y1B]
BUSY signal
Important
Use the hardware stroke limit function when carrying out JOG operation near the
upper or lower limits. (Refer to section 12.4.4).
* If the hardware stroke limit function is not used, the workpiece may exceed the
operating range, causing an accident.
JOG operation
In JOG operation, the Forward run JOG start signal (Y16, Y18, Y1A) or Reverse
run JOG start signal (Y17, Y19, Y1B) turns ON, causing position/speed commands
to be output to the servo amplifier from the AD75 while the signal is ON. The
workpiece is then moved in the designated direction.
The following shows examples of JOG operation.
When the START signal turns ON, acceleration begins in the direction designated by the
START signal, and continues for the acceleration time designated in " Pr.33 JOG
1)
operation acceleration time selection". At this time, the BUSY signal changes from OFF to
ON.
When the workpiece being accelerated reaches the speed set in " Cd.19 JOG speed",
the movement continues at this speed.
2)
Constant speed operation takes place at 2) and 3).
When the START signal is turned OFF, deceleration begins from the speed set in
3)
" Cd.19 JOG speed", and continues for the deceleration time designated in " Pr.34 JOG
operation deceleration time selection".
The operation stops when the speed becomes 0. At this time, the BUSY signal changes
4)
from ON to OFF.
1)
ON
OFF
[Y1D]
[X0]
ON
OFF
ON
OFF
OFF
ON
[X4, X5, X6]
OFF
Forward JOG run
2)
3)
4)
Fig. 11.3 JOG operation
11 - 4
Deceleration for the deceleration
time selected in Pr. 34
Reverse JOG run
ON
MELSEC-A