Download Print this page

Mitsubishi A1SD75M3 User Manual page 597

Positioning module

Advertisement

14 TROUBLESHOOTING
Relevant buffer memory address
Axis 1
Axis 2
Axis 3
809
909
1009
78
228
378
80
230
380
81
231
381
74
224
374
75
225
375
1150
1200
1250
76
226
376
77
227
377
1150
1200
1250
Setting range
(Setting given in sequence program)
<Zero point return retry>
0, 1
<Setting for the movement amount after
near-point dog ON>
0 to 2147483647
<Zero point return speed>
1 to 1000000 [pulse/s]
1 to 600000000 [mm/min, etc.]
<Positioning start No.>
1 to 600, 7000 to 7010
8001 to 8050, 9001 to 9003
<Creep speed>
1 to 1000000 [pulse/s]
1 to 600000000 [mm/min, etc.]
<Positioning start No.>
1 to 600, 7000 to 7010
8001 to 8050, 9001 to 9003
14 - 9
Remedy
After making an axis error reset (refer to [3] in Section
14.1), perform manual control operation (refer to Chapter
11) to move the axis to the position where the upper limit
signal (FLS) will not be turned OFF.
After making an axis error reset (refer to [3] in Section
14.1), perform manual control operation (refer to Chapter
11) to move the axis to the position where the lower limit
signal (RLS) will not be turned OFF.
Check the ON/OFF statuses of the stop command (output
signal/external input issued to AD75) and turn OFF the
active stop commands.
• Output signals issued to AD75 ... Axis 1: Y13, Axis 2:
Y14, Axis 3: Y1C
• External inputs ... External device connection connector:
Stop signal (STOP)
After checking the status of the stop command, perform
axis error resetting (refer to [3] in section 14.1) to remove
the error, then turn ON the start signal.
Turn ON the PLC READY signal (Y1D) with the BUSY
signals of all axes OFF.
• Reset the axis error (refer to [3] in section 14.1) to cancel
the error.
• Reexamine the sequence program that has turned ON
the positioning start signal [Y10, Y11, Y12], forward run
JOG start signal [Y16, Y18, Y1A], reverse run JOG start
signal [Y17, Y19, Y1B] or " Cd. 22 Manual pulse
generator enable flag".
• The zero point return retry function (refer to section
12.2.1) is validated (setting: 1).
• Using manual control operation (refer to Chapter 11) to
move from the current position (zero point) and perform
machine zero point return.
• Calculate the distance of travel according to the speed
limit, zero point return speed and deceleration speed,
and determine the movement amount after activation at
the near-point dog so that the distance of travel is larger
than the deceleration distance.
• Set a smaller zero point return speed.
• Adjust the near-point dog position so that the movement
amount after activation at the near-point dog becomes
longer. (Refer to sections 8.2.5 to 8.2.7)
Execute mechanical zero point return (positioning start No.
9001). (Refer to section 8.2)
Correct the creep speed to within the zero point return
speed. (Refer to section 5.2.5)
Execute mechanical zero point return (positioning start No.
9001). (Refer to section 8.2)
MELSEC-A

Hide quick links:

Advertisement

loading

This manual is also suitable for:

A1sd75m2A1sd75m1Ad75m2Ad75m1Ad75m3