5 DATA USED FOR POSITIONING CONTROL
Pr.100 Servo series
Set this parameter to "2: MR-J2-B".
Pr.101 Amplifier setting
Set whether an absolute position detection system is valid or invalid.
When using the servo amplifier in an incremental system, set this parameter to
"0: Absolute position detection invalid".
When using the servo amplifier in an absolute position detection system, set
this parameter to "1: Absolute position detection valid".
Note) A parameter error will occur if "Absolute position detection valid" is
selected for the incremental encoder.
Pr.102 Regenerative brake resister
Select the regenerative brake resistor to be used and whether an external
dynamic brake is valid or invalid.
H
0
Pr.103 Motor type
Set "0080
".
H
Since setting is made as the MR-J2-B on the peripheral device, "00FF
motor" can be selected, but set "0080
"
Pr.104
Motor capacity" and "
servo amplifier.
However, set the "
Pr.104
value "0".
(Refer to the following "
Pr.104 Motor capacity
Set any of 1 to 9999 in hexadecimal.
The value is automatically set in the servo amplifier according to the used
servomotor.
POINT
Always set the motor capacity to other than "0".
At the default value "0", operation cannot be performed since
communication with the servo amplifier is not made.
Regenerative brake option selection
00: External regenerative brake option not used
05: MR-RB32
08: MR-RB30
09: MR-RB50
10: MR-RB032
11: MR-RB12
External dynamic brake valid/invalid selection
0: External dynamic brake invalid
1: External dynamic brake valid
: Automatic setting" (initial setting).
H
Pr.106
Feedback pulse" are automatically set in the
Motor capacity" of the AD75 to other than the initial
Pr.104
Motor capacity".)
5 - 89
MELSEC-A
: Special
H