12 CONTROL AUXILIARY FUNCTIONS
-214748364.8
Unusable range in absolute
position detection system
Example 2.
(1) Using Expression 1, calculate the positioning address that can be specified in
the system where the zero point address in Example 1 is 214740000.0 (µm).
Lower limit value of positioning address
(Positioning address) = 0.1
Upper limit value of positioning address
(Positioning address) = 0.1
(2) Since the lower limit value of the calculated positioning address is within the
range of Condition 2, the calculated address 187896454.4 (µm) is the lower
limit for positioning in the absolute position detection system.
Since the upper limit value of the calculated positioning address is outside the
range of Condition 2, the upper limit value 214748364.7 (µm) in the positioning
range of Condition 2 is the upper limit for positioning in the absolute position
detection system.
Use the AD75 within the range 187896454.4 (µm) to 214748364.7 (µm) in the
absolute position detection system.
For positioning in excess of 187896454.4 (µm), the AD75 cannot be used in
the absolute position detection system.
Positioning address specifying range
187896454.4
Example 3.
(1) The conditions for calculating the positioning address are indicated below.
Movement amount per pulse: 0.9 (µm)
Zero point address: 0.0 (µm)
Number of feedback pulses = 8192 (pulse)
(2) Calculate the positioning address from the range of using the number of output
pulses in Condition 1 and the expression for calculating the positioning
address (Expression 1).
Lower limit value of positioning address (use the number of negative side
pulses in Condition 1 for calculation)
(Positioning address) = (movement amount per pulse)
Upper limit value of positioning address (use the number of positive side
pulses in Condition 1 for calculation)
(Positioning address) = (movement amount per pulse)
( - 268435456) + 214740000.0
= 187896454.4 (µm)
268435455 + 214740000.0
= 241583545.5 (µm)
214748364.7
(Zero point)
214740000.0
Usable range in absolute
position detection system
pulses) + (zero point address)
= 0.9
( - 268435456) + 0.0
= - 241591910.4 (µm)
pulses) + (zero point address)
= 0.9
268435455 + 0.0
= 241591909.5 (µm)
12 - 63
MELSEC-A
241583545.5
Setting cannot
be made
(number of output
(number of output
Unit: µm