10 ADVANCED POSITIONING CONTROL
10.4.2 Condition data setting examples
The following shows setting examples for "condition data".
(1) Setting the device ON/OFF as a condition
[Condition] Device "X0" (=AD75 READY) is ON
Da.14
Condition target
01
: Device X
H
(2) Setting the numeric value stored in the "buffer memory" as a
condition
[Condition]
The value stored in buffer memory addresses "800, 801" (=" Md.29 Current
feed value") is "1000" or larger.
Da.14
Condition target
04
: Buffer memory
H
(2 words)
(3) Designating the axis and positioning data No. to be simultaneously
started in "simultaneous start"
[Condition]
Simultaneously starting "axis 2 positioning data No.3".
Da.14
Condition target
05
: Positioning
H
data No.
Da.15
Da.16
Condition
Address
operator
07
: DEV=ON
–
H
Da.15
Da.16
Condition
Address
operator
≤ P1
03
:
800
H
Da.15
Da.16
Condition
Address
operator
0A
: Axis 2
H
–
designation
10 - 19
MELSEC-A
Da.17
Da.18
Parameter 1
Parameter 2
0
–
Da.17
Da.18
Parameter 1
Parameter 2
1000
–
Da.17
Da.18
Parameter 1
Parameter 2
High-order 16
–
bits "0003
"
H