14 TROUBLESHOOTING
Relevant buffer memory address
Axis 1
Axis 2
Axis 3
6
156
306
7
157
307
8
158
308
9
159
309
10
160
310
11
161
311
12
162
312
13
163
313
16
166
316
17
167
317
18
168
318
19
169
319
20
170
320
21
171
321
22
172
322
23
173
323
24
174
324
25
175
325
Setting range
(Setting given in sequence program)
1 to 1000000 [pulse/s]
1 to 600000000 [mm/min, etc.]
(One-word type) 1 to 65535
(Two-word type) 1 to 8388608
(One-word type) 1 to 65535
(Two-word type) 1 to 8388608
1 to 1000000 [pulse/s]
1 to 600000000 [mm/min, etc.]
• [mm] [inch] [pulse]
-2147483648 to 2147483647
• [degree] 0 to 35999999
• [mm] [inch] [pulse]
-2147483648 to 2147483647
• [degree] 0 to 35999999
0, 1
0, 1
• [mm] [inch] [pulse]
1 to 32767000
• [degree] 1 to 32767
1 to 500
0, 1
14 - 19
Remedy
Change the setting to within the setting range and turn
OFF then ON the PLC READY signal (Y1D).
• Change the setting to within the setting range.
• In case of a unit other than "degree," change the settings
so that the lower limit value is smaller than the upper limit
value.
• When the absolute position restoration mode is the
"infinite length mode", make the software stroke limit
function invalid.
(Refer to section 12.4.3, section 12.6.2.)
• Change the setting to within the setting range.
• Change the settings so that the lower limit value is
smaller than the upper limit value with a unit other than
"degree."
• When the absolute position restoration mode is the
"infinite length mode", make the software stroke limit
function invalid.
(Refer to section 12.4.3, section 12.6.2.)
Change the setting to within the setting range and turn
OFF then ON the PLC READY signal (Y1D).