VLT AQUA Low Harmonic Drive Instruction Manual Contents Contents 1 How to Read the Instruction Manual Copyright, Limitation of Liability and Revision Rights Symbols 2 Safety General Warning Before Commencing Repair Work Special conditions Avoid unintended start Safe Stop Installation...
Page 2
6 How to Program the Low Harmonic Drive How to Program the Adjustable Frequency Drive How to Program the Active Filter Using the Low Harmonic Drive in NPN Mode VLT AQUA Drive - Description of Common Parameters Main Menu Parameter Options 6-48...
Page 3
VLT AQUA Low Harmonic Drive Instruction Manual Contents 13-** Smart Logic Controller 6-56 14-** Special Functions 6-57 15-** FC Information 6-58 16-** Data Readouts 6-59 18-** Info & Readouts 6-60 20-** FC Closed-loop 6-60 21-** Ext. Closed-loop 6-61 22-** Application Functions...
Page 4
VLT AQUA Low Harmonic Drive Instruction Contents Manual ® MG.20.T1.22 - VLT is a registered Danfoss trademark...
Danfoss reserves the right to revise this publication at any time and to make changes to its contents without prior notice or any obligation to notify former or present users of such revisions or changes.
NOTE! The VLT AQUA Low Harmonic Drive has two different LCPs, one for the adjustable frequency drive (to the right) and one for the active filter (to the left). Each LCP controls only the unit it is connected to and there is no communication between the two LCPs 1.1.4 Symbols...
Installation at High Altitudes Installation at high altitude: At altitudes above 9843 ft [3 km], please contact Danfoss Drives regarding PELV. Warning against Unintended Start 1. The motor can be brought to a stop by means of digital commands, bus commands, references or a local stop, while the adjustable frequency drive is connected to line power.
VLT AQUA Low Harmonic Drive Instruction 2 Safety Manual 2.1.2 General Warning Warning: Touching the electrical parts may be fatal - even after the equipment has been disconnected from line power. Also make sure that other voltage inputs have been disconnected, (linkage of DC intermediate circuit), as well as the motor connection for kinetic backup.
VLT AQUA Low Harmonic Drive Instruction Manual 2 Safety Installation requirements: The overall electrical safety of the adjustable frequency drive requires special installation considerations regarding: • Fuses and circuit breakers for overcurrent and short-circuit protection • Selection of power cables (line power, motor, brake, load sharing and relay) •...
Page 10
VLT AQUA Low Harmonic Drive Instruction 2 Safety Manual Figure 2.2: Figure of the essential aspects of an installation to achieve a Stopping Category 0 (EN 60204-1) with safety Category 3 (EN 954-1). ® MG.20.T1.22 - VLT is a registered Danfoss trademark...
VLT AQUA Low Harmonic Drive Instruction Manual 2 Safety 2.1.7 Safe Stop of the Adjustable Frequency Drive For versions fitted with a Safe Stop terminal 37 input, the adjustable frequency drive can perform the safety function Safe Torque Off (As defined by...
VLT AQUA Low Harmonic Drive Instruction 2 Safety Manual 2.1.8 IT Line Power IT line power Do not connect adjustable frequency drives with RFI filters to line power supplies with a voltage between phase and ground of more than 440 V for 400 Vs and 760 V for 690 V drives.
VLT AQUA Low Harmonic Drive Instruction Manual 3 Introduction to the Low Harmonic Drive 3 Introduction to the Low Harmonic Drive 3.1.1 Working Principle The VLT Low Harmonic Drive is a VLT High Power adjustable frequency drive with an integrated active filter. An active filter is a device that actively monitors harmonic distortion levels and injects compensative harmonic current onto the line to cancel out the harmonics.
VLT AQUA Low Harmonic Drive Instruction 3 Introduction to the Low Harmonic Drive Manual 3.1.2 IEEE519 Compliance Low harmonic drives are designed to draw an ideal sinusoidal current waveform from the supply grid with a power factor of 1. Where traditional non- linear load draws pulse-shaped currents, the low harmonic drive compensates for this via the parallel filter path which lowers the stress on the supply grid.
VLT AQUA Low Harmonic Drive Instruction Manual 3 Introduction to the Low Harmonic Drive 3.1.3 Ordering Form Type Code It is possible to design a VLT Low Harmonic Drive according to the application requirements by using the ordering number system.
Page 16
VLT AQUA Low Harmonic Drive Instruction 3 Introduction to the Low Harmonic Drive Manual ® MG.20.T1.22 - VLT is a registered Danfoss trademark...
VLT AQUA Low Harmonic Drive Instruction Manual 4 How to Install 4 How to Install 4.1 How to Get Started 4.1.1 About How to Install This chapter covers mechanical and electrical installations to and from power terminals and control card terminals.
VLT AQUA Low Harmonic Drive Instruction 4 How to Install Manual 4.2 Pre-installation 4.2.1 Planning the Installation Site NOTE! Before performing the installation, it is important to plan the installation of the adjustable frequency drive. Neglecting this may result in extra work during and after installation.
VLT AQUA Low Harmonic Drive Instruction Manual 4 How to Install 4.2.4 Lifting Always lift the adjustable frequency drive using the dedicated lifting holes. For all D and E frames, use a bar to avoid bending the lifting holes of the adjustable frequency drive.
Page 20
VLT AQUA Low Harmonic Drive Instruction 4 How to Install Manual Figure 4.3: Recommended lifting method, frame size F - filter section. Figure 4.4: Recommended lifting method, frame size F - drive section. ® MG.20.T1.22 - VLT is a registered Danfoss trademark...
Page 21
VLT AQUA Low Harmonic Drive Instruction Manual 4 How to Install NOTE! Note the plinth is provided in the same packaging as the adjustable frequency drive but is not attached to frame size F during shipment. The plinth is required to allow airflow to the drive to provide proper cooling. The F frames should be positioned on top of the plinth in the final installation location.
Page 22
VLT AQUA Low Harmonic Drive Instruction 4 How to Install Manual ® MG.20.T1.22 - VLT is a registered Danfoss trademark...
Page 23
VLT AQUA Low Harmonic Drive Instruction Manual 4 How to Install ® MG.20.T1.22 - VLT is a registered Danfoss trademark...
Page 24
VLT AQUA Low Harmonic Drive Instruction 4 How to Install Manual ® MG.20.T1.22 - VLT is a registered Danfoss trademark...
Page 25
VLT AQUA Low Harmonic Drive Instruction Manual 4 How to Install ® MG.20.T1.22 - VLT is a registered Danfoss trademark...
VLT AQUA Low Harmonic Drive Instruction 4 How to Install Manual Mechanical Dimensions and Rated Power Frame size 21/54* 21/54* Enclosure protection NEMA Type 1 Type 1 Normal overload rated power - 250–350 HP [160–250 kW] at 400 V 450–600 HP [315–450 kW] at 400 V 110% overload torque (380–480 V)
Page 27
VLT AQUA Low Harmonic Drive Instruction Manual 4 How to Install Frame size 21/54* Enclosure protection NEMA Type 1 Normal overload rated power - 110% over- 670–952 hp [500–710 kW] at 400 V load torque (380–480 V) Shipping Dimensions - filter...
VLT AQUA Low Harmonic Drive Instruction 4 How to Install Manual 4.3 Mechanical Installation Preparation of the mechanical installation of the adjustable frequency drive must be done carefully to ensure proper results and to avoid additional work during installation. Start by taking a close look at the mechanical drawings at the end of this instruction manual to become familiar with the space demands.
Page 29
VLT AQUA Low Harmonic Drive Instruction Manual 4 How to Install Figure 4.10: Space in front of IP21/IP54 enclosure type, frame size E7. Figure 4.11: Space in front of IP21/IP54 enclosure type, frame size F17. Wire access Ensure that proper cable access is present including the necessary bending allowance.
VLT AQUA Low Harmonic Drive Instruction 4 How to Install Manual 4.3.3 Assembly of F Frame Sections Procedure to attach F frame drive and filter sections together Position filter and drive sections in proximity to one another. The filter section will attach to the left side of the drive section.
Page 31
VLT AQUA Low Harmonic Drive Instruction Manual 4 How to Install Apply gasket to this surface Open doors on LCL side of filter, right most cabinet, and remove indicated shields. Shields to remove Remove indicated inductor module. 4-15 ® MG.20.T1.22 - VLT...
Page 32
VLT AQUA Low Harmonic Drive Instruction 4 How to Install Manual Remove this inductor module After the inductor module is removed, the filter and drive sections can be attached to one another. Four corner brackets and six side brackets will be required for this operation. They will be included in a bag with the appropriate screws. After the internal brackets are installed, the two top “L”...
VLT AQUA Low Harmonic Drive Instruction Manual 4 How to Install 4.3.4 Control Wire Connection between Drive and Filter In order to make the filter start when the drive starts, the control cards of the different sections are connected. For D and E frames these connections and the corresponding programming of the drive are already made at the factory.
VLT AQUA Low Harmonic Drive Instruction 4 How to Install Manual 4.3.5 Terminal Locations - Frame size D Take the following terminal positions into consideration when you design for cable access. Section shown ↓ Figure 4.12: Terminal locations D6 - filter Section shown ↓...
VLT AQUA Low Harmonic Drive Instruction Manual 4 How to Install NOTE! All D frames are available with standard input terminals or disconnect switch 4.3.6 Terminal Locations - Frame size E Give thought to the following terminal positions when designing the cable access.
Page 36
VLT AQUA Low Harmonic Drive Instruction 4 How to Install Manual Section shown ↓ Figure 4.15: Terminal locations E6 - drive Note that the power cables are heavy and difficult to bend. Give thought to the optimum position of the adjustable frequency drive for ensuring easy installation of the cables.
VLT AQUA Low Harmonic Drive Instruction Manual 4 How to Install NOTE! Power connections can be made to positions A or B 4.3.7 Terminal Locations - Frame size F Terminal locations - Filter Figure 4.17: Terminal locations - Filter (left side, front and right side view). The connector plate is 1.65 in Section shown [42 mm] below .0 level.
Page 38
VLT AQUA Low Harmonic Drive Instruction 4 How to Install Manual Terminal locations - Rectifier Figure 4.18: Terminal locations - Rectifier (left side, front and right side view). The connector plate is 1.65 in [42 mm] below .0 level. 1) Load Share Terminal (-)
VLT AQUA Low Harmonic Drive Instruction Manual 4 How to Install Terminal locations - Inverter Section shown Figure 4.19: Terminal locations - Inverter Cabinet (front, left and right side view). The connector plate is ↓ 1.65 in [42 mm] below .0 level.
Page 40
VLT AQUA Low Harmonic Drive Instruction 4 How to Install Manual NOTE! A door fan is required on the enclosure to remove the heat losses not contained in the backchannel of the drive and any additional losses generated from other components installed inside the enclosure. The total required air flow must be calculated so that the appropriate fans can be selected.
Page 41
VLT AQUA Low Harmonic Drive Instruction Manual 4 How to Install External ducts If additional duct work is added externally to the Rittal cabinet, the pressure drop in the ducting must be calculated. Use the charts below to derate the adjustable frequency drive according to the pressure drop.
Page 42
VLT AQUA Low Harmonic Drive Instruction 4 How to Install Manual Figure 4.22: E frame Derating vs. Pressure Change (Large Fan) P355-P450 Drive air flow: 850 cfm (1445 m Figure 4.23: F frame Derating vs. Pressure Change Drive air flow: 580 cfm (985 m 4-26 ®...
Page 43
VLT AQUA Low Harmonic Drive Instruction Manual 4 How to Install 4.3.9 Connector/Conduit Entry - IP21 (NEMA 1) and IP54 (NEMA12) Cables are connected through the gland plate from the bottom. Remove the plate and plan where to place the entry for the connectors or conduits.
Page 44
VLT AQUA Low Harmonic Drive Instruction 4 How to Install Manual Frame size F17 F17: Cable entries viewed from the bottom of the adjustable frequency drive 1) Line cable connection 2) Motor cable connection Figure 4.25: Mounting of bottom plate, E7 The bottom plate of the E frame can be mounted from either inside or outside of the enclosure, allowing flexibility in the installation process, i.e., if...
Page 45
VLT AQUA Low Harmonic Drive Instruction Manual 4 How to Install 4.3.10 IP21 Drip Shield Installation (Frame size D) To comply with the IP21 rating, a separate drip shield is to be installed as explained below: • Remove the two front screws.
VLT AQUA Low Harmonic Drive Instruction 4 How to Install Manual 4.4 Field Installation of Options 4.4.1 Installation of Input Plate Options This section is for the field installation of input option kits available for adjustable frequency drives in all D and E frames.
VLT AQUA Low Harmonic Drive Instruction Manual 4 How to Install 4.5 Frame size F Panel Options Space Heaters and Thermostat Mounted on the cabinet interior of frame size F adjustable frequency drives, space heaters controlled via automatic thermostat help control humidity inside the enclosure, extending the lifetime of drive components in damp environments.
Page 48
VLT AQUA Low Harmonic Drive Instruction 4 How to Install Manual Manual Motor Starters Provide 3-phase power for electric blowers often required for larger motors. Power for the starters is provided from the load side of any supplied contactor, circuit breaker, or disconnect switch. Power is fused before each motor starter, and is off when the incoming power to the drive is off. Up to two starters are allowed (one if a 30 A, fuse-protected circuit is ordered).
VLT AQUA Low Harmonic Drive Instruction Manual 4 How to Install 4.6 Electrical Installation 4.6.1 Power Connections Cabling and Fusing NOTE! Cables General All cabling must comply with national and local regulations on cable cross-sections and ambient temperature. UL applications require 167°F [75°C] copper conductors.
Page 50
VLT AQUA Low Harmonic Drive Instruction 4 How to Install Manual Switching frequency: When adjustable frequency drives are used together with sine-wave filters to reduce the acoustic noise from a motor, the switching frequency must be Switching Frequency set according to the instructions in par. 14-01 Term.
Page 51
VLT AQUA Low Harmonic Drive Instruction Manual 4 How to Install Figure 4.27: Frame size D11 Load sharing option Line AUX Fan Brake option Temp Switch Motor AUX Relay Fan/SMPS fuse 4-35 ® MG.20.T1.22 - VLT is a registered Danfoss trademark...
Page 52
VLT AQUA Low Harmonic Drive Instruction 4 How to Install Manual Figure 4.28: Position of ground terminals (drive section) Figure 4.29: Frame size E7 4-36 ® MG.20.T1.22 - VLT is a registered Danfoss trademark...
Page 53
VLT AQUA Low Harmonic Drive Instruction Manual 4 How to Install Load sharing option Line AUX Fan Brake option Temp Switch Motor AUX Relay Fan/SMPS fuse 4-37 ® MG.20.T1.22 - VLT is a registered Danfoss trademark...
Page 54
VLT AQUA Low Harmonic Drive Instruction 4 How to Install Manual Figure 4.30: Active Filter, frame size F17 Section shown ↓ Line Bus bars to rectifier section of drive Fuse block 4-38 ® MG.20.T1.22 - VLT is a registered Danfoss trademark...
Page 55
VLT AQUA Low Harmonic Drive Instruction Manual 4 How to Install Figure 4.31: Rectifier Cabinet, frame size F17 Section shown ↓ 4-39 ® MG.20.T1.22 - VLT is a registered Danfoss trademark...
Page 56
VLT AQUA Low Harmonic Drive Instruction 4 How to Install Manual 24 V DC, 5 A Load sharing T1 Output Taps Temp Switch 104 105 Control Transformer Fuses (2 or 4 pieces). See fuse tables for part numbers Manual Motor Starters SMPS Fuse.
Page 57
VLT AQUA Low Harmonic Drive Instruction Manual 4 How to Install Figure 4.32: Inverter Cabinet, frame size F17 Section shown ↓ 4-41 ® MG.20.T1.22 - VLT is a registered Danfoss trademark...
Page 58
VLT AQUA Low Harmonic Drive Instruction 4 How to Install Manual External Temperature Monitoring Motor AUX Relay NAMUR NAMUR Fuse. See fuse tables for part numbers AUX Fan Fan Fuses. See fuse tables for part numbers 101 102 103 SMPS Fuses. See fuse tables for part numbers Brake 4.6.2 Grounding...
Page 59
VLT AQUA Low Harmonic Drive Instruction Manual 4 How to Install 4.6.4 RFI Switch Line power supply isolated from ground If the adjustable frequency drive is supplied from an isolated line power source ( IT line power, floating delta and grounded delta) or TT/TN-S line power with grounded leg, the RFI switch is recommended to be turned off (OFF) via par.
Page 60
VLT AQUA Low Harmonic Drive Instruction 4 How to Install Manual 4.6.6 Shielded Cables It is important that shielded and armored cables are connected properly to ensure high EMC immunity and low emissions. Connection can be made using either cable connectors or clamps: •...
Page 61
VLT AQUA Low Harmonic Drive Instruction Manual 4 How to Install F frame Requirements Motor phase cable quantities must be multiples of 2, resulting in 2, 4, 6, or 8 (1 cable is not allowed) to obtain equal amount of wires attached to both inverter module terminals.
Page 62
VLT AQUA Low Harmonic Drive Instruction 4 How to Install Manual 4.6.9 Brake Resistor Temperature Switch Frame size D-E-F Torque: 0.5-0.6 Nm (5 in-lbs) Screw size: M3 This input can be used to monitor the temperature of an externally connected brake resistor. If the connection between 104 and 106 is removed, the adjustable frequency drive will trip on warning/alarm 27, “Brake IGBT”.
VLT AQUA Low Harmonic Drive Instruction Manual 4 How to Install 4.6.11 AC line input connections Line power must be connected to terminals 91, 92 and 93 located on the far left of the unit. Ground is connected to the terminal to the right of terminal Terminal No.
VLT AQUA Low Harmonic Drive Instruction 4 How to Install Manual 4.6.13 Power and Control Wiring for Non-shielded Cables Induced Voltage! Run motor cables from multiple drives separately. Induced voltage from output motor cables run together can charge equipment capacitors even with the equipment turned off and locked out. Failure to run output cables separately could result in death or serious injury.
Short-circuit protection: The adjustable frequency drive must be protected against short-circuit to avoid electrical or fire hazard. Danfoss recommends using the fuses mentioned below to protect service personnel and equipment in case of an internal failure in the drive. The adjustable frequency drive provides full short-circuit protection in case of a short-circuit on the motor output.
Page 66
VLT AQUA Low Harmonic Drive Instruction 4 How to Install Manual Size/Type Bussmann PN* Rating Siba P500 170M8611 1100 A, 1000 V 20 781 32.1000 P560 170M8611 1100 A, 1000 V 20 781 32.1000 P630 170M6467 1400 A, 700 V 20 681 32.1400...
Page 67
VLT AQUA Low Harmonic Drive Instruction Manual 4 How to Install Frame size Bussmann PN* Rating Alternative Fuses LP-CC-6 6 A, 600 V Any listed Class CC, 6 A Table 4.13: Safety Relay Coil Fuse with PILS Relay 4.6.15 Line Power Disconnectors - Frame Size D, E and F Frame size Power &...
Use an insulated bearing as recommended by the motor manufacturer (note: Motors from reputable manufacturers will typically have these fitted as standard in motors of this size) If found to be necessary and after consultation with Danfoss: Lower the IGBT switching frequency Modify the inverter waveform, 60°...
Page 69
VLT AQUA Low Harmonic Drive Instruction Manual 4 How to Install Control card wiring path for the D11 Control card wiring path for the E7 4.6.21 Access to Control Terminals All terminals to the control cables are located beneath the LCP (both filter and drive LCP). They are accessed by opening the door of the unit.
VLT AQUA Low Harmonic Drive Instruction 4 How to Install Manual 4.6.22 Electrical Installation, Control Terminals To connect the cable to the terminal: Strip insulation by about 0.34–0.39 in [9–10 mm] Insert a screwdriver in the square hole. Insert the cable in the adjacent circular hole.
VLT AQUA Low Harmonic Drive Instruction Manual 4 How to Install 4.7 Connection Examples for Control of Motor with External Signal Pro- vider NOTE! The following examples refer only to the drive control card (right LCP), the filter. 4.7.1 Start/Stop...
VLT AQUA Low Harmonic Drive Instruction 4 How to Install Manual 4.8 Electrical Installation - additional 4.8.1 Electrical Installation, Control Cables Figure 4.34: Diagram showing all electrical terminals without options. 1:Connection to filter Safe Stop Installation Terminal 37 is the input to be used for Safe Stop. For instructions on safe stop installation, refer to the section in the adjustable frequency drive Design Guide.
Page 75
VLT AQUA Low Harmonic Drive Instruction Manual 4 How to Install Input polarity of control terminals NOTE! To comply with EMC emission specifications, shielded/armored cables are recommended. If a non-shielded/unarmored cable is used, see section Power and Control Wiring for Non-shielded cables .
VLT AQUA Low Harmonic Drive Instruction 4 How to Install Manual 4.8.2 Switches S201, S202, and S801 Switches S201 (A53) and S202 (A54) are used to select a current (0-20 mA) or a voltage (-10 to 10 V) configuration for the analog input terminals 53 and 54, respectively.
VLT AQUA Low Harmonic Drive Instruction Manual 4 How to Install 4.9 Final Set-up and Test To test the set-up and ensure that the adjustable frequency drive is running, follow these steps. Step 1. Locate the motor nameplate NOTE! The motor is either star- (Y) or delta-connected (Δ). This information is located on the motor nameplate data.
Page 78
"Report Value" in the [Alarm Log] shows the last measuring sequence carried out by the AMA before the adjustable frequency drive entered alarm mode. This number along with the description of the alarm will assist you in troubleshooting. If you contact Danfoss for service, make sure to mention the number and alarm description.
VLT AQUA Low Harmonic Drive Instruction Manual 4 How to Install 4.10 Additional Connections 4.10.1 Mechanical Brake Control In hoisting/lowering applications, it is necessary to be able to control an electro-mechanical brake: • Control the brake using any relay output or digital output (terminal 27 or 29).
VLT AQUA Low Harmonic Drive Instruction 4 How to Install Manual 4.10.3 Motor Thermal Protection The electronic thermal relay in the adjustable frequency drive has received UL-approval for single motor protection, when par. 1-90 Motor Thermal Protection ETR Trip Motor Current is set for and par.
VLT AQUA Low Harmonic Drive Instruction Manual 5 How to Operate the Low Harmonic Drive 5 How to Operate the Low Harmonic Drive 5.1 Ways of Operation 5.1.1 Ways of operation The low harmonic drive can be operated in 2 ways:...
Page 82
VLT AQUA Low Harmonic Drive Instruction 5 How to Operate the Low Harmonic Drive Manual Display lines: Status line: Status messages displaying icons and graphics. Line 1-2: Operator data lines displaying data and variables de- fined or chosen by the user. By pressing the [Status] key, up to one extra line can be added.
Page 83
VLT AQUA Low Harmonic Drive Instruction Manual 5 How to Operate the Low Harmonic Drive Status display I This readout state is standard after startup or initialization. Use [INFO] to obtain information about the value/measurement linked to the displayed operating variables (1.1, 1.2, 1.3, 2, and 3).
Page 84
VLT AQUA Low Harmonic Drive Instruction 5 How to Operate the Low Harmonic Drive Manual LEDs: If certain threshold values are exceeded, the alarm and/or warning LED lights up. A status and alarm text appear on the control panel. The On LED is activated when the adjustable frequency drive receives power from AC line voltage, a DC bus terminal, or an external 24 V supply. At the same time, the back light is on.
Page 85
VLT AQUA Low Harmonic Drive Instruction Manual 5 How to Operate the Low Harmonic Drive [Alarm Log] displays an alarm list of the five latest alarms (numbered A1-A5). To obtain additional details about an alarm, use the arrow keys to navigate to the alarm number and press [OK].
Page 86
VLT AQUA Low Harmonic Drive Instruction 5 How to Operate the Low Harmonic Drive Manual NOTE! External stop signals activated by means of control signals or a serial bus will override a “start” command via the LCP. [Off] stops the connected motor (when pressed on the drive LCP) or the filter (when pressed on the filter LCP). The key can be...
Page 87
VLT AQUA Low Harmonic Drive Instruction Manual 5 How to Operate the Low Harmonic Drive 5.1.4 Changing a text value If the selected parameter is a text value, it can be changed by using the up/down navigation keys. The up key increases the value, and the down key decreases the value.
VLT AQUA Low Harmonic Drive Instruction 5 How to Operate the Low Harmonic Drive Manual 5.1.7 Readout and programming of indexed parameters Parameters are indexed when placed in a rolling stack. Fault Log: Error Code Fault Log: Time Par. 15-30 to par.
Page 89
VLT AQUA Low Harmonic Drive Instruction Manual 5 How to Operate the Low Harmonic Drive Data transfer from LCP to adjustable frequency drive: LCP Copy Go to par. 0-50 Press the [OK] key Select “All from LCP” Press the [OK] key The parameter settings stored in the GLCP are now transferred to the adjustable frequency drive indicated by the progress bar.
Page 90
VLT AQUA Low Harmonic Drive Instruction 5 How to Operate the Low Harmonic Drive Manual 5.1.11 RS-485 Bus Connection Both filter portion and adjustable frequency drive can be connected to a controller (or master) together with other loads using the RS-485 stand- ard interface.
Page 91
5.1.13 PC software tools PC-based Configuration Tool MCT 10 The low harmonic drive is equipped with two serial communication ports. Danfoss provides a PC tool for communication between PC and adjustable Available Literature frequency drive, PC-based Configuration Tool MCT 10. Please check the section on for detailed information on this tool.
Page 92
Smart Logic Controller Set-up Ordering number: Please order the CD containing MCT 10 Set-up Software using code number 130B1000. WWW.DANFOSS.COM, Business Area: Motion Controls MCT 10 can also be downloaded from the Danfoss website: 5-12 ® MG.20.T1.22 - VLT is a registered Danfoss trademark...
VLT AQUA Low Harmonic Drive Instruction Manual 6 How to Program the Low Harmonic Drive 6 How to Program the Low Harmonic Drive 6.1 How to Program the Adjustable Frequency Drive 6.1.1 Parameter Set-up Overview of parameter groups Group Title...
Page 94
VLT AQUA Low Harmonic Drive Instruction 6 How to Program the Low Harmonic Drive Manual 6.1.2 Quick Menu Mode The GLCP provides access to all parameters listed under the Quick Menus. To set parameters using the [Quick Menu] button: Pressing [Quick Menu] the list indicates the different areas contained in the quick menu.
Page 95
VLT AQUA Low Harmonic Drive Instruction Manual 6 How to Program the Low Harmonic Drive 6.1.3 Q1 My Personal Menu Parameters defined by the user can be stored in Q1 My Personal Menu. My Personal Menu Select to display only the parameters, which have been pre-selected and programmed as personal parameters. For example, a pump or equipment OEM may have pre-programmed these to be in My Personal Menu during factory commissioning to make on-site commissioning / fine tuning simpler.
Page 96
VLT AQUA Low Harmonic Drive Instruction 6 How to Program the Low Harmonic Drive Manual 6.1.5 Q3 Function Set-ups The function set-up provides quick and easy access to all parameters required for the majority of water and wastewater applications including variable torque, constant torque, pumps, dosing pumps, well pumps, booster pumps, mixer pumps, aeration blowers and other pump and fan applications.
Page 97
VLT AQUA Low Harmonic Drive Instruction Manual 6 How to Program the Low Harmonic Drive The Function Set-up parameters are grouped in the following way: Q3-1 General Settings Q3-10 Clock Settings Q3-11 Display Settings Q3-12 Analog Output Q3-13 Relays Relay 1 ⇒ 5-40 Function Relay 0-70 Set Date and Time 0-20 Display Line 1.1 Small...
Page 98
VLT AQUA Low Harmonic Drive Instruction 6 How to Program the Low Harmonic Drive Manual Q5-3 Input Assignments Analog Input 53 Analog Input 54 6.1.7 Q6 Loggings Q6 Loggings can be used for fault finding. Please notice that the parameters listed in the table for Q6 below only serve as examples since they will vary depending on the programming of the particular adjustable frequency drive.
Page 99
VLT AQUA Low Harmonic Drive Instruction Manual 6 How to Program the Low Harmonic Drive 6.1.9 Parameter Selection In main menu mode, the parameters are divided into groups. Select a Group no. Parameter group: parameter group using the navigation keys.
VLT AQUA Low Harmonic Drive Instruction 6 How to Program the Low Harmonic Drive Manual 6.2 How to Program the Active Filter The factory settings for the filter part of the Low Harmonic Drive are chosen for optimal operation with a minimum of additional programming. All CT- values, as well as frequency, voltage levels and other values directly linked to the drive configuration are pre-set.
VLT AQUA Low Harmonic Drive Instruction Manual 6 How to Program the Low Harmonic Drive 6.3 VLT AQUA Drive - Description of Common Parameters 6.3.1 Main Menu ® The main menu includes all available parameters in the VLT AQUA Drive FC 200 adjustable frequency drive.
Page 102
VLT AQUA Low Harmonic Drive Instruction 6 How to Program the Low Harmonic Drive Manual [46] Hungarian Part of Language package 3 [47] Czech Part of Language package 3 [48] Polish Part of Language package 4 [49] Russian Part of Language package 3...
Page 103
VLT AQUA Low Harmonic Drive Instruction Manual 6 How to Program the Low Harmonic Drive [1618] Motor Thermal Thermal load on the motor, calculated by the ETR function. See also parameter group 1-9* Motor Temperature. [1622] Torque [%] Shows the actual torque produced, in percentage.
Page 104
VLT AQUA Low Harmonic Drive Instruction 6 How to Program the Low Harmonic Drive Manual [1682] Serial com. bus REF 1 Main reference value sent with control word via the serial communications network, e.g., from the BMS, PLC or other master controller.
Page 105
VLT AQUA Low Harmonic Drive Instruction Manual 6 How to Program the Low Harmonic Drive 0-23 Display Line 2 Large Option: Function: Select a variable for display in line 2. Display Line 1.1 Small [1615] * Frequency The options are the same as those listed for par. 0-20...
Page 106
VLT AQUA Low Harmonic Drive Instruction 6 How to Program the Low Harmonic Drive Manual 0-71 Date Format Option: Function: [0] * YYYY-MM-DD Sets the date format to be used in the LCP. DD-MM-YYYY Sets the date format to be used in the LCP.
Page 107
VLT AQUA Low Harmonic Drive Instruction Manual 6 How to Program the Low Harmonic Drive NOTE! This parameter cannot be changed when the motor is running. NOTE! When set for closed-loop, the commands reversing and start reversing will not reverse the direction of the motor.
Page 108
VLT AQUA Low Harmonic Drive Instruction 6 How to Program the Low Harmonic Drive Manual 1-25 Motor Nominal Speed Range: Function: Application [100 - 60000 RPM] Enter the nominal motor speed value from the motor nameplate data. This data is used for calcu- dependent* lating automatic motor compensations.
Page 109
VLT AQUA Low Harmonic Drive Instruction Manual 6 How to Program the Low Harmonic Drive Application Examples > Automatic Motor Adaptation See section: in the Design Guide. 6.3.4 3-0* Reference Limits Parameters for setting the reference unit, limits and ranges.
Page 110
VLT AQUA Low Harmonic Drive Instruction 6 How to Program the Low Harmonic Drive Manual 3-41 Ramp 1 Ramp-up Time Range: Function: Application [Application dependant] Enter the ramp-up time, i.e., the acceleration time from 0 RPM to par. 1-25 Motor Nominal Speed...
Page 111
VLT AQUA Low Harmonic Drive Instruction Manual 6 How to Program the Low Harmonic Drive 3-86 Check Valve Ramp End Speed [RPM] Range: Function: 0 [RPM]* [0 – Motor Speed Low Limit [RPM]] Set the speed in [RPM] below Motor Speed Low Limit where the Check Valve is expected to be closed and the Check Valve no longer shall be active.
Page 112
VLT AQUA Low Harmonic Drive Instruction 6 How to Program the Low Harmonic Drive Manual 3-88 Final Ramp Time Range: Function: 0 [s]* [0 – 60 [s]] Enter the Final Ramp Time to be used when ramping down from Motor Speed Low Limit, par. 4-11 or 4-12, to zero speed.
Page 113
VLT AQUA Low Harmonic Drive Instruction Manual 6 How to Program the Low Harmonic Drive 6.3.6 5-** Digital In/Out Parameter group for configuring the digital input and output. 5-01 Terminal 27 Mode Option: Function: [0] * Input Defines terminal 27 as a digital input.
Page 114
VLT AQUA Low Harmonic Drive Instruction 6 How to Program the Low Harmonic Drive Manual Functions dedicated to only one digital input are stated in the associated parameter. All digital inputs can be programmed to these functions: No operation No reaction to signals transmitted to terminal.
Page 115
VLT AQUA Low Harmonic Drive Instruction Manual 6 How to Program the Low Harmonic Drive Preset ref. bit Preset ref. 0 Preset ref. 1 Preset ref. 2 Preset ref. 3 Preset ref. 4 Preset ref. 5 Preset ref. 6 Preset ref. 7...
Page 116
VLT AQUA Low Harmonic Drive Instruction 6 How to Program the Low Harmonic Drive Manual [55] DigiPot Increase Uses the input as an INCREASE signal to the Digital Potentiometer function described in parameter group 3-9* [56] DigiPot Decrease Uses the input as a DECREASE signal to the Digital Potentiometer function described in parameter...
Page 117
VLT AQUA Low Harmonic Drive Instruction Manual 6 How to Program the Low Harmonic Drive 5-14 Terminal 32 Digital Input Option: Function: [0] * No Operation Same options and functions as par. 5-1* Digital Inputs , except for Pulse input...
Page 118
VLT AQUA Low Harmonic Drive Instruction 6 How to Program the Low Harmonic Drive Manual [30] Brake Fault (IGBT) [35] External Interlock [36] Control Word Bit 11 [37] Control Word Bit 12 [40] Out of Ref. Range [41] Below Reference, low [42] Above Ref.
Page 119
VLT AQUA Low Harmonic Drive Instruction Manual 6 How to Program the Low Harmonic Drive [199] Pipe Filling [211] Cascade Pump1 [212] Cascade Pump2 [213] Cascade Pump3 [223] Alarm, Trip Locked [224] Bypass Mode Active 5-53 Term. 29 High Ref./Feedb. Value...
Page 120
VLT AQUA Low Harmonic Drive Instruction 6 How to Program the Low Harmonic Drive Manual 6-10 Terminal 53 Low Voltage Range: Function: 0.07 V* [Application dependant] Enter the low voltage value. This analog input scaling value should correspond to the low reference/ feedback value set in par.
Page 121
VLT AQUA Low Harmonic Drive Instruction Manual 6 How to Program the Low Harmonic Drive 6-24 Terminal 54 Low Ref./Feedb. Value Range: Function: 0.000* [-999999.999 - 999999.999 ] Enter the analog input scaling value that corresponds to the low voltage/low current value set in par.
Page 122
VLT AQUA Low Harmonic Drive Instruction 6 How to Program the Low Harmonic Drive Manual [143] Ext. CL 1 4-20 mA 0 - 100% [144] Ext. CL 2 4-20 mA 0 - 100% [145] Ext. CL 3 4-20 mA 0 - 100% NOTE! Values for setting the minimum reference are found in open-loop par.
Page 123
VLT AQUA Low Harmonic Drive Instruction Manual 6 How to Program the Low Harmonic Drive EXAMPLE 3: Variable value= REFERENCE, range= Min ref - Max ref Range needed for output= Min ref (0%) - Max ref (100%), 0–10 mA Terminal 42 Output Min Scale Output signal 0 or 4 mA is needed at Min ref - set par.
Page 124
VLT AQUA Low Harmonic Drive Instruction 6 How to Program the Low Harmonic Drive Manual 6.3.9 Drive Closed-loop, 20-** This parameter group is used for configuring the closed-loop PID controller, which controls the output frequency of the adjustable frequency drive.
Page 125
VLT AQUA Low Harmonic Drive Instruction Manual 6 How to Program the Low Harmonic Drive [132] lb/h [140] ft/s [141] ft/min [145] [160] °F [170] [171] lb/in [172] in WG [173] ft WG [174] in Hg [180] This parameter determines the unit that is used for the setpoint reference and feedback that the PID controller will use for controlling the output frequency of the adjustable frequency drive.
Page 126
VLT AQUA Low Harmonic Drive Instruction 6 How to Program the Low Harmonic Drive Manual 20-93 PID Proportional Gain Range: Function: 0.50* [0.00 - 10.00 ] Maximum Reference/Feedb. If (Error x Gain) jumps with a value equal to what is set in par. 20-14...
Page 127
VLT AQUA Low Harmonic Drive Instruction Manual 6 How to Program the Low Harmonic Drive NOTE! It is important that the par. 4-13 Motor Speed High Limit [RPM] or par. 4-14 Motor Speed High Limit [Hz] is set to the max. operational...
Page 128
VLT AQUA Low Harmonic Drive Instruction 6 How to Program the Low Harmonic Drive Manual 22-24 No-Flow Delay Range: Function: 10 s* [1 - 600 s] Set the time. Low Power/Low Speed must remain detected to activate signal for actions. If detection disappears before the timer runs out, the timer will be reset.
Page 129
VLT AQUA Low Harmonic Drive Instruction Manual 6 How to Program the Low Harmonic Drive 22-32 Low Speed [RPM] Range: Function: Application [Application dependant] To be used if par. 0-02 Motor Speed Unit has been set for RPM (parameter not visible if Hz selected).
Page 130
VLT AQUA Low Harmonic Drive Instruction 6 How to Program the Low Harmonic Drive Manual 22-39 High Speed Power [HP] Range: Function: Application [Application dependant] To be used if par. 0-03 Regional Settings has been set for North America (parameter not visible if dependent* International selected).
Page 131
VLT AQUA Low Harmonic Drive Instruction Manual 6 How to Program the Low Harmonic Drive 22-45 Setpoint Boost Range: Function: 0 %* [-100 - 100 %] Only to be used if par. 1-00 Configuration Mode , is set for closed-loop and the integrated PI con- troller is used.
Page 132
VLT AQUA Low Harmonic Drive Instruction 6 How to Program the Low Harmonic Drive Manual 22-51 End of Curve Delay Range: Function: 10 s* [0 - 600 s] When an end of curve condition is detected, a timer is activated. When the time set in this parameter...
Page 133
VLT AQUA Low Harmonic Drive Instruction Manual 6 How to Program the Low Harmonic Drive From the data sheet showing characteristics for the specific equipment at different speeds, simply reading across from the H point and the Q point allows us to find point A, which is the...
Page 134
VLT AQUA Low Harmonic Drive Instruction 6 How to Program the Low Harmonic Drive Manual 22-84 Speed at No-Flow [Hz] Range: Function: Application [Application dependant] Resolution 0.033 Hz. dependent* The speed of the motor at which flow has effectively stopped and minimum pressure H...
Page 135
VLT AQUA Low Harmonic Drive Instruction Manual 6 How to Program the Low Harmonic Drive 22-90 Flow at Rated Speed Range: Function: 0.000* [0.000 - 999999.999 ] Enter the value corresponding to Flow at Rated Speed. This value can be defined using the pump datasheet.
Page 136
VLT AQUA Low Harmonic Drive Instruction 6 How to Program the Low Harmonic Drive Manual 23-01 ON Action Arra [10] Option: Function: SL Controller Action Select the action during ON Time. See par. 13-52 for descriptions of the options. [0] *...
Page 137
VLT AQUA Low Harmonic Drive Instruction Manual 6 How to Program the Low Harmonic Drive 23-02 OFF Time Array [10] Range: Function: Application [Application dependant] Sets the OFF time for the timed action. dependent* NOTE! The adjustable frequency drive has no backup of the clock function and the set...
Page 138
VLT AQUA Low Harmonic Drive Instruction 6 How to Program the Low Harmonic Drive Manual [39] Set digital out B high [40] Set digital out C high [41] Set digital out D high [42] Set digital out E high [43]...
Page 139
VLT AQUA Low Harmonic Drive Instruction Manual 6 How to Program the Low Harmonic Drive 6.3.12 Water Application Functions, 29-** The group contains parameters used for monitoring water/wastewater applications. 29-00 Pipe Fill Enable Option: Function: [0] * Disabled Select Enabled to fill pipes at a user-specified rate.
VLT AQUA Low Harmonic Drive Instruction 6 How to Program the Low Harmonic Drive Manual 6.4 Parameter Options 6.4.1 Default settings Changes during operation: ”TRUE” means that the parameter can be changed while the adjustable frequency drive is in operation and “FALSE” means that the adjustable frequency drive must be stopped before a change can be made.
VLT AQUA Low Harmonic Drive Instruction Manual 6 How to Program the Low Harmonic Drive 6.4.2 0-** Operation and Display Par. Parameter description Default value 4 set-up Change during Conver- Type No. # (SR = Size related) operation sion index...
VLT AQUA Low Harmonic Drive Instruction 6 How to Program the Low Harmonic Drive Manual 6.4.3 1-** Load / Motor Par. Parameter description Default value 4 set-up Change dur- Conver- Type No. # (SR = Size related) ing operation sion index...
VLT AQUA Low Harmonic Drive Instruction Manual 6 How to Program the Low Harmonic Drive 6.4.4 2-** Brakes Par. Parameter description Default value 4 set-up Change dur- Conver- Type No. # (SR = Size related) ing operation sion index 2-0* DC Brake...
VLT AQUA Low Harmonic Drive Instruction Manual 6 How to Program the Low Harmonic Drive 6.4.7 5-** Digital In / Out Par. Parameter description Default value 4 set-up Change dur- Conver- Type No. # (SR = Size related) ing operation...
VLT AQUA Low Harmonic Drive Instruction 6 How to Program the Low Harmonic Drive Manual 6.4.8 6-** Analog In / Out Par. Parameter description Default value 4 set-up Change dur- Conver- Type No. # (SR = Size related) ing operation...
VLT AQUA Low Harmonic Drive Instruction Manual 6 How to Program the Low Harmonic Drive 6.4.9 8-** Communication and Options Par. Parameter description Default value 4 set-up Change during Conver- Type No. # (SR = Size related) operation sion index...
VLT AQUA Low Harmonic Drive Instruction 6 How to Program the Low Harmonic Drive Manual 6.4.10 9-** Profibus Par. Parameter description Default value 4 set-up Change during Conver- Type No. # (SR = Size related) operation sion index 9-00 Setpoint...
VLT AQUA Low Harmonic Drive Instruction Manual 6 How to Program the Low Harmonic Drive 6.4.12 14-** Special Functions Par. Parameter description Default value 4 set-up Change dur- Conver- Type No. # (SR = Size related) ing operation sion index...
VLT AQUA Low Harmonic Drive Instruction 6 How to Program the Low Harmonic Drive Manual 6.4.13 15-** FC Information Par. Parameter description Default value 4 set-up Change during Conver- Type No. # (SR = Size related) operation sion index 15-0* Operating Data...
VLT AQUA Low Harmonic Drive Instruction Manual 6 How to Program the Low Harmonic Drive 6.4.14 16-** Data Readouts Par. Parameter description Default value 4 set-up Change dur- Conver- Type No. # (SR = Size related) ing operation sion index...
VLT AQUA Low Harmonic Drive Instruction 6 How to Program the Low Harmonic Drive Manual 6.4.15 18-** Info & Readouts Par. Parameter description Default value 4 set-up Change dur- Conver- Type No. # (SR = Size related) ing operation sion index...
VLT AQUA Low Harmonic Drive Instruction Manual 6 How to Program the Low Harmonic Drive 6.4.17 21-** Ext. Closed-loop Par. Parameter description Default value 4 set-up Change dur- Conver- Type No. # (SR = Size related) ing operation sion index 21-0* Ext.
VLT AQUA Low Harmonic Drive Instruction 6 How to Program the Low Harmonic Drive Manual 6.4.18 22-** Application Functions Par. Parameter description Default value 4 set-up Change dur- Conver- Type No. # (SR = Size related) ing operation sion index...
VLT AQUA Low Harmonic Drive Instruction Manual 6 How to Program the Low Harmonic Drive 6.4.19 23-** Time-based Funtions Par. Parameter description Default value 4 set-up Change during Conver- Type No. # (SR = Size related) operation sion index 23-0* Timed Actions...
VLT AQUA Low Harmonic Drive Instruction 6 How to Program the Low Harmonic Drive Manual 6.4.20 25-** Cascade Controller Par. Parameter description Default value 4 set-up Change during Conver- Type No. # (SR = Size related) operation sion index 25-0* System Settings...
VLT AQUA Low Harmonic Drive Instruction Manual 6 How to Program the Low Harmonic Drive 6.4.21 26-** Analog I / O Option MCB 109 Par. Parameter description Default value 4 set-up Change dur- Conver- Type No. # (SR = Size related)
VLT AQUA Low Harmonic Drive Instruction Manual 6 How to Program the Low Harmonic Drive 6.5.2 Digital In/Out 5-** Par. Parameter description Default value 4 set-up FC 302 Change dur- Conver- Type No. # (SR = Size related) only ing opera-...
VLT AQUA Low Harmonic Drive Instruction 6 How to Program the Low Harmonic Drive Manual 6.5.4 Special Functions 14-** Par. Parameter description Default value 4 set-up FC 302 Change dur- Conver- Type No. # (SR = Size related) only ing opera-...
VLT AQUA Low Harmonic Drive Instruction Manual 6 How to Program the Low Harmonic Drive 6.5.5 FC Information 15-** Par. Parameter description Default value 4 set-up FC 302 Change during Conver- Type No. # (SR = Size related) only operation...
VLT AQUA Low Harmonic Drive Instruction 6 How to Program the Low Harmonic Drive Manual 6.5.6 Data Readouts 16-** Par. Parameter description Default value 4 set-up FC 302 Change dur- Conver- Type No. # (SR = Size related) only ing opera-...
VLT AQUA Low Harmonic Drive Instruction Manual 6 How to Program the Low Harmonic Drive 6.5.8 AF Readouts301-** Par. No. Parameter description Default value 4 set-up FC 302 Change Conver- Type (SR = Size related) only during op- sion index...
Page 164
VLT AQUA Low Harmonic Drive Instruction 6 How to Program the Low Harmonic Drive Manual 6-72 ® MG.20.T1.22 - VLT is a registered Danfoss trademark...
VLT AQUA Low Harmonic Drive Instruction Manual 7 RS-485 Installation and Set-up 7 RS-485 Installation and Set-up 7.1.1 Overview RS-485 is a two-wire bus interface compatible with multi-drop network topology, i.e., nodes can be connected as a bus, or via drop cables from a common trunk line.
Page 166
VLT AQUA Low Harmonic Drive Instruction 7 RS-485 Installation and Set-up Manual 7.1.2 Network Connection Connect the adjustable frequency drive to the RS-485 network as follows (see also diagram): Connect signal wires to terminal 68 (P+) and terminal 69 (N-) on the main control board of the adjustable frequency drive.
Page 167
VLT AQUA Low Harmonic Drive Instruction Manual 7 RS-485 Installation and Set-up 7.1.3 RS-485 Bus Termination Use the terminator dip switch on the main control board of the adjustable frequency drive to terminate the RS-485 bus. NOTE! The factory setting for the dip switch is OFF.
Page 168
When crossing is unavoidable, the RS-485 cable must cross motor and brake resistor cables at an angle of 90 degrees. The adjustable frequency drive protocol, also referred to as adjustable frequency drive bus or standard bus, is the Danfoss standard serial communication bus.
VLT AQUA Low Harmonic Drive Instruction Manual 7 RS-485 Installation and Set-up 7.3 Network Configuration 7.3.1 FC 300 Adjustable Frequency Drive Set-up Set the following parameters to enable the Adjustable Frequency protocol for the adjustable frequency drive. Parameter Number Setting Par.
Page 170
VLT AQUA Low Harmonic Drive Instruction 7 RS-485 Installation and Set-up Manual 7.4.3 Message Length (LGE) The message length is the number of data bytes plus the address byte ADR and the data control byte BCC. The length of messages with 4 data bytes is...
Page 171
VLT AQUA Low Harmonic Drive Instruction Manual 7 RS-485 Installation and Set-up 7.4.6 The Data Field The structure of data blocks depends on the type of message. There are three message types, and the type applies for both control messages (mas- ter=>slave) and response messages (slave=>master).
Page 172
VLT AQUA Low Harmonic Drive Instruction 7 RS-485 Installation and Set-up Manual 7.4.7 The PKE Field The PKE field contains two sub-fields: Parameter command and response AK, and Parameter number PNU: Bits no. 12-15 transfer parameter commands from master to slave and return processed slave responses to the master.
Page 173
VLT AQUA Low Harmonic Drive Instruction Manual 7 RS-485 Installation and Set-up PWE low (Hex) Fault Report The parameter number used does not exit. There is no write access to the defined parameter. Data value exceeds the parameter's limits. The sub index used does not exit.
Page 174
VLT AQUA Low Harmonic Drive Instruction 7 RS-485 Installation and Set-up Manual 7.4.11 Data Types Supported by FC 300 Unsigned means that there is no operational sign in the message. Data types Description Integer 16 Integer 32 Unsigned 8 Unsigned 16...
VLT AQUA Low Harmonic Drive Instruction Manual 7 RS-485 Installation and Set-up 7.5 Examples 7.5.1 Writing a Parameter Value Motor Speed High Limit [Hz] Change par. 4-14 to 100 Hz. Write the data in EEPROM. Motor Speed High Limit PKE = E19E Hex - Write single word in par. 4-14...
VLT AQUA Low Harmonic Drive Instruction 7 RS-485 Installation and Set-up Manual 7.6 How to Access Parameters 7.6.1 Parameter Handling The PNU (Parameter Number) is translated from the register address contained in the Modbus read or write message. The parameter number is translated to Modbus as (10 x parameter number) DECIMAL.
VLT AQUA Low Harmonic Drive Instruction Manual 8 General Specifications 8 General Specifications Line power supply (L1, L2, L3): Supply voltage 380–480 V +5% AC line voltage low / line drop-out: During low AC line voltage or a line drop-out, the adjustable frequency drive continues until the intermediate circuit voltage drops below the minimum stop level, which corresponds typically to 15% below the adjustable frequency drive's lowest rated supply voltage.
Page 178
VLT AQUA Low Harmonic Drive Instruction 8 General Specifications Manual 1) Terminals 27 and 29 can also be programmed as output. Analog inputs: Number of analog inputs Terminal number 53, 54 Modes Voltage or current Mode select Switch S201 and switch S202...
Page 179
VLT AQUA Low Harmonic Drive Instruction Manual 8 General Specifications Control card, RS-485 serial communication: Terminal number 68 (P,TX+, RX+), 69 (N,TX-, RX-) Terminal number 61 Common for terminals 68 and 69 The RS-485 serial communication circuit is functionally seated from other central circuits and galvanically isolated from the supply voltage (PELV).
Page 180
VLT AQUA Low Harmonic Drive Instruction 8 General Specifications Manual Control characteristics: Resolution of output frequency at 0–1000 Hz : +/- 0.003 Hz : ≤ 2 ms System response time (terminals 18, 19, 27, 29, 32, 33) Speed control range (open-loop)
Page 181
VLT AQUA Low Harmonic Drive Instruction Manual 8 General Specifications Line Power Supply 3 x 380–480 V AC P160 P200 P250 Typical Shaft output at 400 V [kW] Typical Shaft output at 460 V [HP] Enclosure IP21 Enclosure IP54 Output current...
Page 182
VLT AQUA Low Harmonic Drive Instruction 8 General Specifications Manual Line Power Supply 3 x 380–480 V AC P315 P355 P400 P450 Typical Shaft output at 400 V [kW] Typical Shaft output at 460 V [HP] Enclosure IP21 EnclosureIP54 Output current...
Page 183
VLT AQUA Low Harmonic Drive Instruction Manual 8 General Specifications Line Power Supply 3 x 380–480 V AC P500 P560 P630 P710 Typical Shaft output at 400 V [kW] Typical Shaft output at 460 1000 V [HP] Enclosure IP21, 54...
Page 184
VLT AQUA Low Harmonic Drive Instruction 8 General Specifications Manual 8.2 Filter Specifications Frame size Voltage [V] 380 - 480 380 - 480 380 - 480 Current, RMS [A] Nominal value Peak Current [A] Amplitude value of the current RMS overload [%]...
Via a digital input with the “Reset” function. Via serial communication/optional serial communication bus. By resetting automatically using the [Auto Reset] function, which is a default setting for VLT AQUA Drive, see par. 14-20 Reset Mode AQUA Drive Programming Guide NOTE! After a manual reset using the [RESET] button on the LCP, the [AUTO ON] or [HAND ON] button must be pressed to restart the motor.
Page 186
VLT AQUA Low Harmonic Drive Instruction 9 Troubleshooting Manual Description Warning Alarm/Trip Alarm/Trip Lock Parameter Reference 10 Volts low Live zero error 6-01 No motor 1-80 Line phase loss 14-12 DC link voltage high DC link voltage low DC overvolt...
Page 187
VLT AQUA Low Harmonic Drive Instruction Manual 9 Troubleshooting Description Warning Alarm/Trip Alarm/Trip Lock Parameter Reference Overload Trip Brake IGBT Heatsink temp Heatsink sensor Pwr.card supply Pwr.card temp Illegal PS config New spare part New Type Code Table 9.2: Alarm/Warning code list...
Page 188
VLT AQUA Low Harmonic Drive Instruction 9 Troubleshooting Manual 9.1.1 Fault messages WARNING 1, 10 volts low Troubleshooting: Connect a brake resistor The control card voltage is below 10 V from terminal 50. Remove some of the load from terminal 50, as the 10 V supply is over- Extend the ramp time loaded.
Page 189
Check if the motor is overheating. or software. Check if the motor is mechanically overloaded. Record the value of the following parameters and contact your Danfoss Check that the thermistor is connected correctly between ter- supplier: minal 53 or 54 (analog voltage input) and terminal 50 (+10 V...
Page 190
Brake Resistor Temperature Switch. ALARM 38, Internal fault WARNING/ALARM 28, Brake check failed It may be necessary to contact your Danfoss supplier. Some typical alarm Brake resistor fault: the brake resistor is not connected or not working. messages: Check parameter 2-15, Brake Check.
Page 191
The 24 VDC is measured on the control card. The external 24 VDC backup 2314 Missing power unit data from power unit power supply may be overloaded, otherwise contact your Danfoss sup- 2315 Missing SW version from power unit 2316 Missing io_statepage from power unit plier.
Page 192
VLT AQUA Low Harmonic Drive Instruction 9 Troubleshooting Manual ALARM 53, AMA big motor ALARM 68, Safe stop activated The motor is too big for the AMA to be carried out. Safe stop has been activated. To resume normal operation, apply 24 VDC...
Page 193
VLT AQUA Low Harmonic Drive Instruction Manual 9 Troubleshooting ALARM 93, Dry pump ALARM 246, Power card supply A no-flow situation and high speed indicates that the pump has run dry. This alarm is only for F Frame drives. It is equivalent to Alarm 46. The See parameter group 22-2.
VLT AQUA Low Harmonic Drive Instruction 9 Troubleshooting Manual 9.2 Alarms and Warnings - Filter (left LCP) NOTE! This sections covers warnings and alarms on the filter side LCP. For warning and alarms for the adjustable frequency drive, please see previous section.
Page 195
VLT AQUA Low Harmonic Drive Instruction Manual 9 Troubleshooting Description Warning Alarm/Trip Alarm/Trip Lock Parameter Reference 10 Volts low Live zero error 6-01 Mains phase loss DC link voltage high DC link voltage low DC overvoltage DC undervoltage Overcurrent Ground fault...
Page 196
VLT AQUA Low Harmonic Drive Instruction 9 Troubleshooting Manual LED indication Warning yellow Alarm flashing red Trip locked yellow and red Alarm Word and Extended Status Word Alarm Word Warning Word Extended Status Word 00000001 Line Power Cont. Fault Reserved...
Page 197
VLT AQUA Low Harmonic Drive Instruction Manual 9 Troubleshooting 9.2.1 Fault messages WARNING 1, 10 volts low ALARM 33, Inrush fault Check whether a 24 Volt external DC supply has been connected. The control card voltage is below 10 V from terminal 50.
Page 198
VLT AQUA Low Harmonic Drive Instruction 9 Troubleshooting Manual ALARM 68, Safe stop activated ALARM 250, New spare part Safe stop has been activated. To resume normal operation, apply 24 VDC The power or switch mode power supply has been exchanged. The ad- to terminal 37, then send a reset signal (via Bus, Digital I/O, or by press- justable frequency drive type code must be restored in the EEPROM.
Page 199
VLT AQUA Low Harmonic Drive Instruction Manual 9 Troubleshooting ALARM 316, CT Location Error The Auto CT function could not determine the correct locations of the CTs. ALARM 317, CT Polarity Error The Auto CT function could not determine the correct polarity of the CTs.
Page 200
VLT AQUA Low Harmonic Drive Instruction 9 Troubleshooting Manual 9-16 ® MG.20.T1.22 - VLT is a registered Danfoss trademark...
VLT AQUA Low Harmonic Drive Instruction Manual Index Index 24 Vdc Power Supply 4-32 30 Ampere, Fuse-protected Terminals 4-32 Ac Line Input Connections 4-47 Acceleration Time 6-18 Access To Control Terminals 4-53 Af Readouts 6-71 Af Settings 6-70 Airflow 4-24...
Page 202
VLT AQUA Low Harmonic Drive Instruction Index Manual Dc Link 9-4, 9-13 Default Settings 6-48 Default Settings Digital In/out 6-67 Digital Inputs: Digital Output Display Line 1.1 Small, 0-20 6-10 Display Line 1.2 Small, 0-21 6-12 Display Line 1.3 Small, 0-22...
Page 203
VLT AQUA Low Harmonic Drive Instruction Manual Index [High Speed Rpm] 22-36 6-37 How To Connect A Pc To The Adjustable Frequency Drive 5-10 How To Operate The Graphical Lcp (glcp) Iec Emergency Stop With Pilz Safety Relay 4-31 Index (ind)
Page 204
VLT AQUA Low Harmonic Drive Instruction Index Manual Motor Bearing Currents 4-52 Motor Cable 4-44 Motor Current 1-24 6-15 Motor Nameplate 4-61 Motor Nominal Speed 1-25 6-16 Motor Output [Motor Power Kw] 1-20 6-15 Motor Protection [Motor Speed High Limit Rpm] 4-13...
Page 205
VLT AQUA Low Harmonic Drive Instruction Manual Index Q1 My Personal Menu Q2 Quick Set-up Q3 Function Set-ups Q5 Changes Made Q6 Loggings Quick Menu 5-4, 6-1, 6-2 Quick Menu Mode Quick Transfer Of Parameter Settings When Using Glcp Ramp 1 Ramp-down Time 3-42...
Page 206
VLT AQUA Low Harmonic Drive Instruction Index Manual Terminal 42 Output 6-50 6-29 Terminal 42 Output Max Scale 6-52 6-30 Terminal 42 Output Min Scale 6-51 6-30 Terminal 53 High Ref./feedb. Value 6-15 6-28 Terminal 53 High Voltage 6-11 6-28 Terminal 53 Low Ref./feedb.