F4: Analog Output Option; F5: Digital Output Option - YASKAWA GA800 Technical Reference

Ac drive for industrial applications
Hide thumbs Also See for GA800:
Table of Contents

Advertisement

11.9 F: Options
No.
Name
(Hex.)
F3-22
Terminal DC Function
Selection
(0BEF)
Expert
F3-23
Terminal DD Function
Selection
(0BF0)
Expert
F3-24
Terminal DE Function
Selection
(0BF1)
Expert
F3-25
Terminal DF Function
Selection
(0BF2)
Expert

F4: Analog Output Option

No.
Name
(Hex.)
F4-01
Terminal V1 Function
Selection
(0391)
F4-02
Terminal V1 Gain
(0392)
RUN
F4-03
Terminal V2 Function
Selection
(0393)
F4-04
Terminal V2 Gain
(0394)
RUN
F4-05
Terminal V1 Bias
(0395)
RUN
F4-06
Terminal V2 Bias
(0396)
RUN
F4-07
Terminal V1 Signal Level
(0397)
F4-08
Terminal V2 Signal Level
(0398)

F5: Digital Output Option

No.
Name
(Hex.)
F5-01
Terminal P1-PC Function
Select
(0399)
F5-02
Terminal P2-PC Function
Select
(039A)
574
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function for terminal DC of the DI-A3 option when F3-01 = 8 [Digital Input
Function Selection = Multi-Function Digital Input].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function for terminal DD of the DI-A3 option when F3-01 = 8 [Digital Input
Function Selection = Multi-Function Digital Input].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function for terminal DE of the DI-A3 option when F3-01 = 8 [Digital Input
Function Selection = Multi-Function Digital Input].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function for terminal DF of the DI-A3 option when F3-01 = 8 [Digital Input
Function Selection = Multi-Function Digital Input].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the monitor signal output from terminal V1.
Set the x-xx part of the Ux-xx [Monitor]. For example, set F4-01 = 102 to monitor U1-02
[Output Frequency].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the gain of the monitor signal that is sent from terminal V1. Sets the analog signal
output level from the terminal V1 at 10 V or 20 mA as 100% when an output for
monitoring items is 100%.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the monitor signal output from terminal V2.
Set the x-xx part of the Ux-xx [Monitor]. For example, set F4-03 = 103 to monitor U1-03
[Output Current].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the gain of the monitor signal that is sent from terminal V2. Sets the analog signal
output level from terminal V2 at 10 V or 20 mA as 100% when an output for monitoring
items is 100%.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the bias of the monitor signal that is sent from terminal V1. When an output for
monitoring items is 0%, this parameter sets the analog signal output level from the V1
terminal as a percentage of 10 V or 20 mA.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the bias of the monitor signal that is sent from terminal V2. Set the level of the analog
signal sent from the V2 terminal at 10 V or 20 mA as 100% when an output for monitoring
items is 0%.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the output signal level for terminal V1.
0 : 0 to 10 V
1 : -10 to 10 V
V/f
CL-V/f
OLV
CLV
AOLV
Sets the output signal level for terminal V2.
0 : 0 to 10 V
1 : -10 to 10 V
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function of terminal P1-PC on the DO-A3 option. Set F5-09 = 2 [DO-A3 Output
Mode Selection = Programmable (F5-01 to F5-08)] to enable this function.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function of terminal P2-PC on the DO-A3 option. Set F5-09 = 2 [DO-A3 Output
Mode Selection = Programmable (F5-01 to F5-08)] to enable this function.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
YASKAWA SIEPC71061737D GA800 Drive Technical Reference
Default
Ref.
(Range)
F
853
(1 - 19F)
F
853
(1 - 19F)
F
853
(1 - 19F)
F
853
(1 - 19F)
Default
Ref.
(Range)
102
854
(000 - 999)
100.0%
854
(-999.9 - +999.9%)
103
855
(000 - 999)
50.0%
855
(-999.9 - +999.9%)
0.0%
855
(-999.9 - +999.9%)
0.0%
855
(-999.9 - +999.9%)
0
856
(0, 1)
0
856
(0, 1)
Default
Ref.
(Range)
0
857
(0 - 1A7)
1
857
(0 - 1A7)

Advertisement

Table of Contents
loading

Table of Contents