E: Motor Parameters; E1: V/F Pattern For Motor 1 - YASKAWA GA800 Technical Reference

Ac drive for industrial applications
Hide thumbs Also See for GA800:
Table of Contents

Advertisement

12.6

E: Motor Parameters

E parameters cover drive input voltage, V/f pattern, and motor parameters.

E1: V/f Pattern for Motor 1

E1 parameters set the drive input voltage and motor V/f characteristics. To switch drive operation from one motor to
another motor, set the V/f characteristics for motor 1.
V/f Pattern Settings
The drive uses a V/f pattern to adjust the output voltage relative to the frequency reference.
This product has been preconfigured with 15 voltage/frequency (V/f) patterns. Use E1-03 [V/f Pattern Selection] to
select the V/f pattern that is appropriate for the application.
Additionally, one custom V/f pattern is available. Set E1-03 = F [Custom] and then manually set parameters E1-04 to
E1-10.
Setting
Specification
Value
Const Trq, 50Hz base, 50Hz max
0
Const Trq, 60Hz base, 60Hz max
1
Const Trq, 50Hz base, 60Hz max
2
Const Trq, 60Hz base, 72Hz max
3
VT, 50Hz, 65% Vmid reduction
4
VT, 50Hz, 50% Vmid reduction
5
VT, 60 Hz, 65% Vmid reduction
6
VT, 60 Hz, 50% Vmid reduction
7
8
High Trq, 50Hz, 25% Vmin boost
9
High Trq, 50Hz, 65% Vmin boost
A
High Trq, 60Hz, 25% Vmin boost
B
High Trq, 60Hz, 65% Vmin boost
High Freq, 60Hz base, 90Hz max
C
High Freq, 60Hz base, 120Hz max
D
High Freq, 60Hz base, 180Hz max
E
Custom
F
YASKAWA SIEPC71061737D GA800 Drive Technical Reference
Table 12.41 Predefined V/f Patterns
Characteristic
Constant torque
For general purpose applications. This pattern is used when the load torque is constant without
any rotation speed such as that used for linear conveyor systems.
Derated torque
This pattern is used for torque loads proportional to 2 or 3 times the rotation speed, such as is the
characteristics
case with fans and pumps.
High starting torque
This pattern is used when strong torque is required during startup.
Constant output
This pattern is used to rotate motors at greater than 60 Hz. Output voltage is constant when
operating at greater than 60 Hz.
Constant torque
Enables a custom V/f pattern by changing E1-04 to E1-13 [V/f Pattern for Motor 1]. The default
settings for E1-04 to E1-13 are the same as Setting Value 1 [Const Trq, 60Hz base, 60Hz max].
12.6 E: Motor Parameters
Application
12
817

Advertisement

Table of Contents
loading

Table of Contents