YASKAWA GA800 Technical Reference page 326

Ac drive for industrial applications
Hide thumbs Also See for GA800:
Table of Contents

Advertisement

6.3 MEMOBUS/Modbus Communications
Note:
Set the reserved bit to 0. Do not write the data in the reserved register or the monitor register.
Register No.
(Hex.)
0000
Reserved
Run command, multi-function input command
bit 0
bit 1
bit 2
bit 3
bit 4
0001
bit 5
bit 6
bit 7
bit 8
bit 9
bit A
bit B
bit C - F
0002
Frequency Reference
0003
Output voltage gain
0004
Torque reference/torque limit (0.1% signed)
0005
Torque compensation (0.1% signed)
0006
PID setpoint (0.01% signed)
0007
Setting for the multi-function analog monitor output terminal 1 (10 V/4000 H)
0008
Setting for the multi-function analog monitor output terminal 2 (10 V/4000 H)
326
Table 6.15 MEMOBUS/Modbus Communications Command Data
When H5-12 = 0, Forward run/stop
1: Forward run, 0: Stop
When H5-12 = 1, run/stop
1: Run, 0: Stop
When H5-12 = 0, Reverse run/stop
1: Reverse run, 0: Stop
When H5-12 = 1, Forward/Reverse run
1: Reverse, 0: Forward run
External fault
1: EF0 [Option Card External Fault]
Fault Reset
1: Reset command
Multi-function input 1
When H1-01 = 40 [Forward Run Command (2-Wire Seq)], the multi-function input command is "ComRef."
Note:
When you switch the bit ON as ComRef, the frequency reference source changes to MEMOBUS/Modbus communications.
When you connect a communication option to the drive, the frequency reference source gives priority to the communications
option.
Multi-function input 2
When the multi-function input command is H1-02 = 41 [Reverse Run Command (2-Wire Seq)], bit 5 is "ComCtrl."
Note:
When you switch the bit ON as ComCtrl, the Run Command source changes to MEMOBUS/Modbus communications. When
you connect a communication option to the drive, the Run Command source gives priority to the communications option.
Multi-function input 3
Multi-function input 4
Multi-function input 5
Multi-function input 6
Multi-function input 7
Multi-function input 8
Reserved
o1-03 [Frequency Display Unit Selection] (unsigned) sets the units.
Units: 0.1%
Setting range: 20 (2.0%) to 2000 (200.0%), the default value at energize: 1000 (100.0%)
Description
YASKAWA SIEPC71061737D GA800 Drive Technical Reference