11.10 H: Terminal Functions
Setting Value
Function
10B
!Overheat Alarm (oH2)
10C
!Analog Terminal Enable
Selection
10D
!Ignore Speed Fdbk (V/f
w/o Enc)
10E
!ASR Integral Reset
110
!Up Command
111
!Down Command
114
!Fault Reset
116
!Motor 2 Selection
118
!Timer Function
119
!PID Disable
11A
!Accel/Decel Time
Selection 2
11B
!Programming Lockout
11E
!Reference Sample Hold
130
!PID Integrator Reset
131
!PID Integrator Hold
132
!Multi-Step Speed
Reference 4
592
V/f
CL-V/f
OLV
CLV
AOLV
Sets the drive to display an oH2 [Drive Overheat Warning] alarm when the input terminal deactivates. The alarm does
not have an effect on drive operation.
V/f
CL-V/f
OLV
CLV
AOLV
Enables and disables the terminal selected with the H3-14 [Analog Input Term Enable Select] function.
ON : Input to the terminal selected with H3-14 is disabled
OFF : Input to the terminal selected with H3-14 is enabled
V/f
CL-V/f
OLV
CLV
AOLV
When the terminal deactivates, the drive ignores the feedback control from the encoder and operates in V/f control.
When the terminal activates, the drive uses the feedback from the encoder to control the motor speed again.
ON : Speed feedback control enable (Closed Loop V/f Control)
OFF : Speed feedback control disable (V/f Control)
V/f
CL-V/f
OLV
CLV
AOLV
Sets the command to reset the integral value and use PI control or P control for the speed control loop.
ON : PI control
OFF : P control
V/f
CL-V/f
OLV
CLV
AOLV
Set this function and 111 [! Down Command] together. Sets the Up command and Down command to use the two push
button switches to increase and decrease the drive frequency reference.
ON : Holds the current frequency reference.
OFF : Increases the frequency reference.
V/f
CL-V/f
OLV
CLV
AOLV
Set this function and 110 [!Up Command] together. Sets the Up command and Down command to use the two push
button switches to increase and decrease the drive frequency reference.
ON : Holds the current frequency reference.
OFF : Decreases the frequency reference.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the command to reset the current fault when the Run command is not active.
Note:
The drive ignores the fault reset command when the Run command is active. Remove the Run command before
you try to reset a fault.
V/f
CL-V/f
OLV
CLV
AOLV
Switches between motor 1 or motor 2. Switch the motor while the motor is stopped.
ON : Selects motor 1
OFF : Selects motor 2
V/f
CL-V/f
OLV
CLV
AOLV
Sets the command to start the timer function. Use this setting with H2-xx = 112 [!Timer Output].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the command to disable PID control with an external input when b5-01 = 1 to 8 [PID Function Setting =
Enabled].
ON : PID control enabled
OFF : PID control disabled
V/f
CL-V/f
OLV
CLV
AOLV
Set this function and H1-xx = 107 [!Accel/Decel Time Selection 1] together. Sets the drive to use C1-01 to C1-08
[Acceleration/Deceleration Times 1 to 4].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the command to prevent parameter changes when the terminal is OFF. You can continue to view parameter setting
values when the terminal is ON [Parameter Write Prohibit].
ON : Parameter Write Prohibit
OFF : Programming Lockout
V/f
CL-V/f
OLV
CLV
AOLV
Samples the analog frequency reference input to the terminals A1, A2, or A3, and continues operation at the sampled
frequency.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the command to reset and hold the PID control integral to 0 when the terminal deactivates.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the command to hold the integral value of the PID control while the terminal deactivates.
V/f
CL-V/f
OLV
CLV
AOLV
Uses a combination of multi-step speed references 1, 2 and 3 (N.C.) to switch d1-09 to d1-16 [Reference 9 to 16].
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
YASKAWA SIEPC71061737D GA800 Drive Technical Reference
Ref.
904
904
904
904
904
904
904
904
904
904
904
904
904
904
904
904

Advertisement