PID Control Applications
Table 12.24
shows applications for PID control.
Application
Speed Control
Pressure control
Flow control
Temperature control
Input Methods for the PID Setpoint
Use b5-01 [PID Mode Setting] to select how the PID setpoint is input to the drive.
When b5-01 = 1 or 2 [Standard or Standard (D on feedback)], either the frequency reference set in b1-01 [Frequency
Reference Selection 1] or b1-15 [Frequency Reference Selection 2] will be the PID setpoint, or the one of the inputs in
Table 12.25
will be the PID setpoint.
When b5-01 = 3 or 4 [Fref + PID Trim or Fref + PID Trim (D on feedback)], one of the inputs in
the PID setpoint.
Input Methods for the PID Setpoint
MFAI terminal A1
MFAI terminal A2
MFAI terminal A3
MEMOBUS/Modbus register 0006H
Pulse train input terminal RP
b5-19 [PID Setpoint Value]
Note:
If you set two inputs for the PID setpoint, it will trigger operation error oPE07 [Analog Input Selection Error].
Entering the PID Feedback Value
You can use two methods to input the PID feedback value to the drive.
YASKAWA SIEPC71061737D GA800 Drive Technical Reference
Figure 12.34 PID Control Operation
Table 12.24 PID Control Applications
Control Content
• The drive uses a feedback signal for the machine speed,
and adjusts that speed to align with the target value.
• The drive uses speed data from other machinery as the
target value to do synchronous control. The drive then
adds that target value to the feedback from the machine
it is operating to align its speed with the other
machinery.
The drive uses feedback from the actual pressure to hold
constant pressure.
The drive uses feedback from the actual flow to hold
constant flow.
The drive uses feedback from the actual temperature to
control a fan and hold constant temperature.
Table 12.25 Input Methods for the PID Setpoint
Set H3-02 = C [Terminal A1 Function Selection = PID Setpoint].
Set H3-10 [Terminal A2 Function Selection] = C .
Set H3-06 [Terminal A3 Function Selection] = C.
Sets MEMOBUS/Modbus register 000FH (Control Selection Setting) bit 1 to 1 (PID
setpoint input). Enters the PID setpoint to MEMOBUS/Modbus register 0006H (PID
Target, 0.01% units, signed).
Set H6-01 = 2 [Terminal RP Pulse Train Function = PID Setpoint Value].
Set b5-18 = 1 [b5-19 PID Setpoint Selection = Enabled]. Enters the PID setpoint to b5-19.
12.3 b: Application
Sensors Used
Tacho generator
Pressure sensor
Flow rate sensor
Thermocoupler, thermistor
Table 12.25