YASKAWA GA800 Technical Reference page 595

Ac drive for industrial applications
Hide thumbs Also See for GA800:
Table of Contents

Advertisement

No.
Name
(Hex.)
H2-09
Modbus Register 2
Address Select
(0B3C)
H2-10
Modbus Register 2 Bit
Select
(0B3D)
H2-20
Comparator 1 Monitor
Selection
(1540)
H2-21
Comparator 1 Lower
Limit
(1541)
H2-22
Comparator 1 Upper
Limit
(1542)
H2-23
Comparator 1 Hysteresis
(1543)
H2-24
Comparator 1 On-Delay
Time
(1544)
H2-25
Comparator 1 Off-Delay
Time
(1545)
H2-26
Comparator 2 Monitor
Selection
(1546)
H2-27
Comparator 2 Lower
Limit
(1547)
H2-28
Comparator 2 Upper
Limit
(1548)
H2-29
Comparator 2 Hysteresis
(1549)
H2-30
Comparator 2 On-Delay
Time
(154A)
H2-31
Comparator 2 Off-Delay
Time
(154B)
H2-32
Comparator 1 Filter Time
(159A)
H2-33
Comparator1 Protection
Selection
(159B)
H2-34
Comparator 2 Filter Time
(159C)
H2-35
Comparator2 Protection
Selection
(159D)
H2-36
Comparator 1 Ineffective
Time
(159E)
H2-37
Comparator 2 Ineffective
Time
(159F)
YASKAWA SIEPC71061737D GA800 Drive Technical Reference
Description
V/f
CL-V/f
OLV
CLV
AOLV
Sets the address of the MEMOBUS/Modbus register output to the MFDO terminal.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the bit of the MEMOBUS/Modbus register output to the MFDO terminal.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the monitor number for comparator 1. Set the x-xx part of the Ux-xx [Monitor]. For
example, set H2-20 = 102 to monitor U1-02 [Output Frequency].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the lower limit detection level for comparator 1 when the full scale analog output for
the monitor selected in H2-20 [Comparator 1 Monitor Selection] is the 100% value.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the upper limit detection level for comparator 1 when the full scale analog output for
the monitor selected in H2-20 [Comparator 1 Monitor Selection] is the 100% value.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the hysteresis level for comparator 1 as a percentage of the full scale analog output for
the monitor selected in H2-20 [Comparator 1 Monitor Selection].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the on-delay time for comparator 1.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the off-delay time for comparator 1.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the monitor number for comparator 2. Set the x-xx part of the Ux-xx [Monitor]. For
example, set H2-26 = 103 to monitor U1-03 [Output Current].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the lower limit detection level for comparator 2 as a percentage of the full scale
analog output for the monitor selected in H2-26 [Comparator 2 Monitor Selection].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the upper limit detection level for comparator 2 as a percentage of the full scale
analog output for the monitor selected in H2-26 [Comparator 2 Monitor Selection].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the hysteresis level for comparator 2 as a percentage of the full scale analog output for
the monitor selected in H2-26 [Comparator 2 Monitor Selection].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the on-delay time for comparator 2.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the off-delay time for comparator 2.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the time constant that is applied to the primary delay filter used for the analog output
of the monitor selected with H2-20 [Comparator 1 Monitor Selection].
V/f
CL-V/f
OLV
CLV
AOLV
Sets drive operation when it detects CP1 [Comparator1 Limit Fault].
0 : Ramp to Stop
1 : Coast to Stop
2 : Fast Stop (Use C1-09)
3 : Alarm Only
4 : Digital Output Only
V/f
CL-V/f
OLV
CLV
AOLV
Sets the time constant that is applied to the primary delay filter used for the analog output
of the monitor selected with H2-26 [Comparator 2 Monitor Selection].
V/f
CL-V/f
OLV
CLV
AOLV
Sets drive operation when it detects CP2 [Comparator2 Limit Fault].
0 : Ramp to Stop
1 : Coast to Stop
2 : Fast Stop (Use C1-09)
3 : Alarm Only
4 : Digital Output Only
V/f
CL-V/f
OLV
CLV
AOLV
Sets the length of time that CP1 [Comparator1 Limit Fault] is disabled.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the length of time that CP2 [Comparator2 Limit Fault] is disabled.
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
11.10 H: Terminal Functions
Default
Ref.
(Range)
0001
908
(0001 - 1FFF)
0000
908
(0000 - FFFF)
102
908
(000 - 999)
0.0%
909
(0.0 - 300.0%)
0.0%
909
(0.0 - 300.0%)
0.0%
909
(0.0 - 10.0%)
0.0 s
909
(0.0 - 600.0 s)
0.0 s
909
(0.0 - 600.0 s)
103
909
(000 - 999)
0.0%
910
(0.0 - 300.0%)
0.0%
910
(0.0 - 300.0%)
0.0%
910
(0.0 - 10.0%)
0.0 s
910
(0.0 - 600.0 s)
0.0 s
910
(0.0 - 600.0 s)
0.0s
910
(0.0 - 10.0 s)
4
911
(0 - 4)
0.0s
911
(0.0 - 10.0 s)
4
911
(0 - 4)
0.0 s
912
(0.0 - 1000.0 s)