No.
Name
(Hex.)
F1-11
Speed Deviation Detect
DelayTime
(038A)
F1-12
Encoder 1 Gear Teeth 1
(038B)
F1-13
Encoder 2 Gear Teeth 1
(038C)
F1-14
Encoder Open-Circuit
Detect Time
(038D)
F1-17
Deviation 2 Detection
Selection
(03AC)
F1-18
Deviation 3 Detection
Selection
(03AD)
F1-19
Deviation 4 Detection
Selection
(03AE)
F1-20
Encoder 1 PCB
Disconnect Detect
(03B4)
F1-21
Encoder 1 Signal
Selection
(03BC)
F1-30
Motor 2 Encoder PCB
Port Select
(03AA)
F1-31
Encoder 2 Pulse Count
(PPR)
(03B0)
F1-32
Encoder 2 Rotation
Selection
(03B1)
F1-33
Encoder 2 Gear Teeth 1
(03B2)
F1-34
Encoder 2 Gear Teeth 2
(03B3)
F1-35
Encoder 2 Pulse Monitor
Scaling
(03BE)
F1-36
Encoder 2 PCB
Disconnect Detect
(03B5)
YASKAWA SIEPC71061737D GA800 Drive Technical Reference
Description
V/f
CL-V/f
OLV
CLV
AOLV
Sets the length of time that the difference between the frequency reference and speed
feedback must be more than the level in F1-10 to cause dEv [Speed Deviation].
Note:
If A1-02 = 0 [Control Method Selection = V/f], you must set H6-01 = 3 [Terminal RP
Pulse Train Function = Speed Feedback (V/F Control)] to enable this parameter.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the number of gear teeth on the motor side. This parameter and F1-13 [Encoder 1
Gear Teeth 2] set the gear ratio between the motor and encoder.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the number of gear teeth on the load side. This parameter and F1-12 [Encoder 1 Gear
Teeth 1] set the gear ratio between the motor and encoder.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the length of time that the drive must not receive a pulse signal to cause PGo
[Encoder (PG) Feedback Loss].
Note:
Motor speed and load conditions can cause ov [Overvoltage] and oC [Overcurrent]
faults.
If A1-02 = 0 [Control Method Selection = V/f], you must set H6-01 = 3 [Terminal RP
Pulse Train Function = Speed Feedback (V/F Control)] to enable this parameter.
V/f
CL-V/f
OLV
CLV
AOLV
Usually it is not necessary to change this setting. Sets the number of motor rotations that
the drive will detect more than one Z pulse per rotation to detect dv2.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the number of rotations necessary to detect conditions that invert the torque reference
and rate of acceleration and cause dv3 [Inversion Detection].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the number of pulses necessary to cause dv4 [Inversion Prevention Detection].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function that enables and disables detection of a disconnected encoder connection
cable to cause PGoH [Encoder (PG) Hardware Fault].
0 : Disabled
1 : Enabled
V/f
CL-V/f
OLV
CLV
AOLV
Sets the number of channels for the signal to the encoder option card.
0 : A Pulse Detection
1 : AB Pulse Detection
V/f
CL-V/f
OLV
CLV
AOLV
Sets the drive port to install the motor 2 encoder option card.
0 : CN5-C
1 : CN5-B
V/f
CL-V/f
OLV
CLV
AOLV
Sets the number of output pulses for each motor revolution for motor 2.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the output sequence for the A and B pulses from the encoder for motor 2. This
parameter assumes that the motor is operating in the forward direction.
0 : Pulse A leads in FWD Direction
1 : Pulse B leads in FWD Direction
V/f
CL-V/f
OLV
CLV
AOLV
Sets the number of gear teeth on the motor side for motor 2. This parameter and F1-34
[Encoder 2 Gear Teeth 2] set the gear ratio between the motor and encoder.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the number of gear teeth on the load side for motor 2. This parameter and F1-33
[Encoder 2 Gear Teeth 1] set the gear ratio between the motor and encoder.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the ratio between the pulse input and the pulse output of the encoder as a 3-digit
number for motor 2. The first digit is the numerator and the second and third digits set the
denominator.
The dividing ratio = (1 + x)/yz when the setting value is a 3-digit value (xyz).
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function that enables and disables detection of a disconnected encoder connection
cable to cause PGoH [Encoder (PG) Hardware Fault] for motor 2.
0 : Disabled
1 : Enabled
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
11.9 F: Options
Default
Ref.
(Range)
0.5 s
842
(0.0 - 10.0 s)
0
842
(0 - 1000)
0
843
(0 - 1000)
2.0 s
843
(0.0 - 10.0 s)
10
843
(0 - 100)
10
843
(0 - 10)
128
844
(0 - 5000)
1
844
(0, 1)
0
844
(0, 1)
1
844
(0, 1)
1024 ppr
844
(1 - 60000 ppr)
0
844
(0, 1)
0
845
(0 - 1000)
0
845
(0 - 1000)
001
845
(001 - 032, 102 - 132 (1 -
1/32))
1
845
(0, 1)
571