12.6 E: Motor Parameters
E3-09: Motor 2 Minimum Output Frequency
No.
Name
(Hex.)
E3-09
Motor 2 Minimum Output
Frequency
(031F)
E3-10: Motor 2 Minimum Output Voltage
No.
Name
(Hex.)
E3-10
Motor 2 Minimum Output
Voltage
(0320)
E3-11: Motor 2 Mid Point B Frequency
No.
Name
(Hex.)
E3-11
Motor 2 Mid Point B
Frequency
(0345)
Expert
Note:
• Set this parameter to 0.0 to disable the function.
• When you initialize the drive, this parameter is reset to the default value.
E3-12: Motor 2 Mid Point B Voltage
No.
Name
(Hex.)
E3-12
Motor 2 Mid Point B Voltage
(0346)
Expert
Note:
• Set this parameter to 0.0 to disable the function.
• When you initialize the drive, this parameter is reset to the default value.
• The setting value changes automatically when you do Auto-Tuning (rotational and stationary 1 or 2).
E3-13: Motor 2 Base Voltage
No.
Name
(Hex.)
E3-13
Motor 2 Base Voltage
(0347)
Expert
Note:
• When you initialize the drive, this parameter is reset to the default value.
• The setting value changes automatically when you do Auto-Tuning (rotational and stationary 1 or 2).

E4: Motor 2 Parameters

E4 parameters [Motor 2 Parameters] set induction motor data. To switch drive operation from one motor to a
different motor, configure motor 2.
Auto-Tuning automatically sets the E4 parameters to the best values for the application. If you cannot do Auto-
Tuning, set the E4 parameters manually.
Note:
E3-xx and E4-xx are available when H1-xx = 16 [MFDI Function Select = Motor 2 Selection].
830
V/f
CL-V/f
OLV
CLV
AOLV
Sets the minimum output frequency for the motor 2 V/f pattern.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the minimum output voltage for the motor 2 V/f pattern.
V/f
CL-V/f
OLV
CLV
AOLV
Sets a middle output frequency for the motor 2 V/f pattern. Set this parameter to adjust the V/f
pattern for the constant output range. Usually it is not necessary to change this parameter.
V/f
CL-V/f
OLV
CLV
AOLV
Sets a middle output voltage for the motor 2 V/f pattern. Set this parameter to adjust the V/f pattern
for the constant output range. Usually it is not necessary to change this parameter.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the base voltage for the motor 2 V/f pattern. Set this parameter to adjust the V/f pattern for the
constant output range. Usually it is not necessary to change this parameter.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
YASKAWA SIEPC71061737D GA800 Drive Technical Reference
Default
(Range)
Determined by E3-01
(0.0 - E3-04)
Default
(Range)
Determined by E3-01
(200 V Class: 0.0 - 255.0 V,
400 V Class: 0.0 - 510.0 V)
Default
(Range)
0.0 Hz
(0.0 - E3-04)
Default
(Range)
0.0 V
(200 V Class: 0.0 to 255.0 V,
400 V Class: 0.0 to 510.0 V)
Default
(Range)
0.0 V
(200 V Class: 0.0 to 255.0 V,
400 V Class: 0.0 to 510.0 V)