YASKAWA GA800 Technical Reference page 843

Ac drive for industrial applications
Hide thumbs Also See for GA800:
Table of Contents

Advertisement

After you set the number of gear teeth, the drive uses this formula to calculate the motor speed:
Note:
When F1-12 = 0 or F1-13 = 0, the gear ratio is 1.
F1-13: Encoder 1 Gear Teeth 2
No.
Name
(Hex.)
F1-13
Encoder 2 Gear Teeth 1
(038C)
After you set the number of gear teeth, the drive uses this formula to calculate the motor speed:
Note:
When F1-12 = 0 or F1-13 = 0, the gear ratio is 1.
F1-14: Encoder Open-Circuit Detect Time
No.
Name
(Hex.)
F1-14
Encoder Open-Circuit Detect
Time
(038D)
If the drive does not detect output pulses from the encoder for longer than the time set in F1-14, the drive will detect
PGo.
Note:
Motor speed and load conditions can cause ov [Overvoltage] and oC [Overcurrent] faults.
F1-17: Deviation 2 Detection Selection
No.
Name
(Hex.)
F1-17
Deviation 2 Detection
Selection
(03AC)
When F1-17 = 0, the drive will not detect dv2.
F1-18: Deviation 3 Detection Selection
No.
Name
(Hex.)
F1-18
Deviation 3 Detection
Selection
(03AD)
When the drive detects these two conditions at the same time for the number of times set in F1-18, the drive will
detect dv3.
• The torque reference and acceleration are in opposite directions. For example, torque reference is in forward run
and the acceleration is in a negative direction.
• The difference between the speed reference and the actual motor speed is more than 30%.
Note:
• Reference the setting value for E5-11 [Encoder Z-Pulse Offset] and the δθ value found on the motor nameplate. A usual cause for a dv3
fault is an incorrect E5-11 setting.
• Set F1-18 = 0 to disable the function.
YASKAWA SIEPC71061737D GA800 Drive Technical Reference
V/f
CL-V/f
OLV
CLV
AOLV
Sets the number of gear teeth on the load side. This parameter and F1-12 [Encoder 1 Gear Teeth 1]
set the gear ratio between the motor and encoder.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the length of time that the drive must not receive a pulse signal to cause PGo [Encoder (PG)
Feedback Loss].
V/f
CL-V/f
OLV
CLV
AOLV
Usually it is not necessary to change this setting. Sets the number of motor rotations that the drive
will detect more than one Z pulse per rotation to detect dv2.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the number of rotations necessary to detect conditions that invert the torque reference and rate of
acceleration and cause dv3 [Inversion Detection].
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
12.7 F: Options
Default
(Range)
0
(0 - 1000)
Default
(Range)
2.0 s
(0.0 - 10.0 s)
Default
(Range)
10
(0 - 100)
Default
(Range)
10
(0 - 10)
12
843