The drive accepts a Run command entered from an external source when setting the parameters in Programming
Mode.
2 : Allow Programming Only at Stop
The drive does not allow the user to enter the Programming Mode while the drive is operating. The keypad does not
display the Programming Mode while the drive is operating.
b1-09: LOCAL/REMOTE Select during RUN
No.
Name
(Hex.)
b1-09
LOCAL/REMOTE Select
during RUN
(0188)
Expert
0 : Disabled
1 : Enabled
When you switch the operation mode from REMOTE to LOCAL during run, the drive writes this REMOTE operation
status to the keypad:
• Frequency reference during run
• RUN/STOP status of the keypad
• FWD/REV
• JOG
Note:
When b1-09 = 1, the drive will detect oPE05 [Run Cmd/Freq Ref Source Sel Err] if you set one of these parameter values:
• b1-02 = 0 [Run Command Selection 1 = Keypad]
• b1-16 = 0 [Run Command Selection 2 = Keypad] and H1-xx = 2 [MFDI Function Selection = External Reference 1/2 Selection]
• H1-xx = 3 to 6, 12, 13, 32 [Multi-Step Speed Reference 1 to 4, Jog Reference Selection, Forward Jog, Reverse Jog]
b1-14: Phase Order Selection
No.
Name
(Hex.)
b1-14
Phase Order Selection
(01C3)
0 : Standard
1 : Switch Phase Order
b1-15: Frequency Reference Selection 2
No.
Name
(Hex.)
b1-15
Frequency Reference
Selection 2
(01C4)
This parameter is enabled when H1-xx = 2 [MFDI Function Selection = External Reference 1/2 Selection] is
activated.
Note:
• Push
on the keypad to set the input mode to LOCAL and enter the frequency reference from the keypad.
• If the frequency reference is 0 Hz or ≤ E1-09 [Minimum Output Frequency] and the drive receives a Run command, the
will flash. Check the setting for the frequency reference input and enter a value more than or equal to E1-09.
0 : Keypad
Use the keypad to enter the frequency reference.
Use
and
on the keypad to change the frequency reference.
YASKAWA SIEPC71061737D GA800 Drive Technical Reference
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function that lets you use the
REMOTE Modes.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the phase order for output terminals U/T1, V/T2, and W/T3. This parameter can align the
Forward Run command from the drive and the forward direction of the motor without changing
wiring.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the input method for frequency reference 2.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
during operation to switch between LOCAL and
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
12.3 b: Application
Default
(Range)
0
(0, 1)
Default
(Range)
0
(0, 1)
Default
(Range)
0
(0 - 4)
on the keypad
12
725