YASKAWA GA800 Technical Reference page 266

Ac drive for industrial applications
Hide thumbs Also See for GA800:
Table of Contents

Advertisement

5.2 European Standards
A - SW (ON)
If you lose an EMC filter switch screw, use
screws with the correct tightening torque.
NOTICE: Only use the screws specified in this manual. If you use screws that are not approved, it can cause damage to the drive.
Model
2004 - 2082, 4002 - 4060
2110 - 2211, 4075 - 4168
2257 - 2415, 4208 - 4720
Installing the External EMC Noise Filter
Drive models 2xxxA and 4xxxA must meet conditions in this section to comply with EN 61800-3:2004+A1:2012.
Connect an EMC noise filter that complies with European standards as specified by Yaskawa to the input side
(primary side). Refer to
External EMC Noise Filter Selection on page 269
Use this procedure to install an EMC noise filter to make equipment and devices added to the drive comply with the
EMC Directive.
1.
Install the drive and EMC noise filter on the same grounded metal plate.
2.
Wire the drive and motor.
3.
Ground the wire shielding on the drive side and motor side.
A - Drive
B - 10 m (32.8 ft) maximum
C - Motor
266
B - Screw (OFF)
Figure 5.16 EMC Filter Switch Location 7
Table 5.11
to find the correct replacement screw and install the new
Table 5.11 Screw Sizes and Tightening Torques
Screw Size
M4 × 20
M4 × 25
M5 × 25
D - Metal conduit
E - Grounding wire
Figure 5.17 Wiring the Drive and Motor
Tightening Torque
to select the correct EMC noise filter.
YASKAWA SIEPC71061737D GA800 Drive Technical Reference
N∙m
1.0 - 1.3
1.0 - 1.3
2.0 - 2.5

Advertisement