YASKAWA GA800 Technical Reference page 855

Ac drive for industrial applications
Hide thumbs Also See for GA800:
Table of Contents

Advertisement

F4-03: Terminal V2 Function Selection
No.
Name
(Hex.)
F4-03
Terminal V2 Function
Selection
(0393)
Set the x-xx part of the Ux-xx [Monitors] to set monitor data to output from the option card. For example, set F4-03 =
103 to monitor U1-03 [Output Current].
Note:
• You cannot use all of the monitors in all of the control methods.
• When you use the terminal in through mode, set this parameter to 000 or 031. You can use this setting to adjust the V2 terminal output from
PLC through MEMOBUS/Modbus communications or a communications option.
F4-04: Terminal V2 Gain
No.
Name
(Hex.)
F4-04
Terminal V2 Gain
(0394)
RUN
The maximum output voltage output from terminal V2 is ±10 V. Use F4-08 [Terminal V2 Signal Level] to set the
signal level.
Example settings:
When you use these settings, and the monitored output voltage is at 100% (drive rated current), the output voltage of
terminal V2 is 5 V (50% of 10 V). The output current is 200% of the drive rated current when terminal V2 outputs a
maximum voltage of 10 V.
• F4-03 [Terminal V2 Function Selection] = 103 (U1-03: Output Current)
• F4-04 = 50.0%
• F4-06 [Terminal V2 Bias] = 0.0%
• F4-08 = 0 (0 V to 10 V)
F4-05: Terminal V1 Bias
No.
Name
(Hex.)
F4-05
Terminal V1 Bias
(0395)
RUN
The maximum output voltage output from terminal V1 is ±10 V. Use F4-07 [Terminal V1 Signal Level] to set the
signal level.
F4-06: Terminal V2 Bias
No.
Name
(Hex.)
F4-06
Terminal V2 Bias
(0396)
RUN
The maximum output voltage output from terminal V2 is ±10 V. Use F4-08 [Terminal V2 Signal Level] to set the
signal level.
YASKAWA SIEPC71061737D GA800 Drive Technical Reference
V/f
CL-V/f
OLV
CLV
AOLV
Sets the monitor signal output from terminal V2.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the gain of the monitor signal that is sent from terminal V2. Sets the analog signal output level
from terminal V2 at 10 V or 20 mA as 100% when an output for monitoring items is 100%.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the bias of the monitor signal that is sent from terminal V1. When an output for monitoring
items is 0%, this parameter sets the analog signal output level from the V1 terminal as a percentage
of 10 V or 20 mA.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the bias of the monitor signal that is sent from terminal V2. Set the level of the analog signal
sent from the V2 terminal at 10 V or 20 mA as 100% when an output for monitoring items is 0%.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
12.7 F: Options
Default
(Range)
103
(000 - 999)
Default
(Range)
50.0%
(-999.9 - +999.9%)
Default
(Range)
0.0%
(-999.9 - +999.9%)
Default
(Range)
0.0%
(-999.9 - +999.9%)
12
855