When the gain set in F2-02 is 100%, the bias set in F2-03 is 30%, and the addition input value is 0%, the frequency
reference is 30% of the maximum output frequency. When the addition input value is 70%, the frequency reference
will be equivalent to the maximum output frequency. The frequency reference will not be more than the maximum
output frequency, although the addition input value is 70% or higher.
F2-02: Analog Input Option Card Gain
No.
Name
(Hex.)
F2-02
Analog Input Option Card
Gain
(0368)
RUN
Note:
Set F2-01 = 1 [Analog Input Function Selection = 3 Channels Added Together] to enable this function.
F2-03: Analog Input Option Card Bias
No.
Name
(Hex.)
F2-03
Analog Input Option Card
Bias
(0369)
RUN
Note:
Set F2-01 = 1 [Analog Input Function Selection = 3 Channels Added Together] to enable this function.

F3: Digital Input Option

F3 parameters set the type of input signal to use with digital input option card DI-A3.
Use these digital inputs to set the frequency reference when you install the DI-A3 card in a drive. Set b1-01 = 3
[Frequency Reference Selection 1 = Option PCB] to use this card as the frequency reference input. The input signal is
isolated input of 24 Vdc and 8 mA.
• Binary, 16-bit/BCD, 4-digit input
• Binary, 12-bit/BCD, 3-digit input
• Binary, 8-bit/BCD, 2-digit input
You can also use the DI-A3 option as an MFDI, if the setting of F3-01 is correct.
On drives with software versions PRG: 09015 and later, without DI-A3 installed, when you set F3-01 = 8 [Digital
Input Function Selection = Multi-Function Digital Input] these functions are enabled:
• H1-40 [Mbus Reg 15C0h bit0 Input Func] to H1-42 [Mbus Reg 15C0h bit2 Input Func]
• H7-01 to H7-04 [Virtual Multi-Function Input 1 to 4]
WARNING! Sudden Movement Hazard. Do test runs and examine the drive to make sure that the command references are correct.
If you set the command reference incorrectly, it can cause damage to the drive or serious injury or death.
MFDI for DI-A3
Set F3-01 = 8 [Digital Input Function Selection = Multi-Function Digital Input] and b1-01 ≠ 3 [Frequency Reference
Selection 1 ≠ Option PCB] to use digital input option DI-A3 as an MFDI.
Use F3-10 to F3-25 [Terminal D0 Function Selection to Terminal DF Function Selection] to set the function for the
DI-A3 terminals.
YASKAWA SIEPC71061737D GA800 Drive Technical Reference
V/f
CL-V/f
OLV
CLV
AOLV
Sets the analog reference gain as a percentage when the maximum output frequency is 100%.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the analog reference bias as a percentage when the maximum output frequency is 100%.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
12.7 F: Options
Default
(Range)
100.0%
(-999.9 - +999.9%)
Default
(Range)
0.0%
(-999.9 - +999.9%)