12.8 H: Terminal Functions
0 : 0.1 kWh units
1 : 1 kWh units
2 : 10 kWh units
3 : 100 kWh units
4 : 1000 kWh units
H2-07: Modbus Register 1 Address Select
No.
Name
(Hex.)
H2-07
Modbus Register 1 Address
Select
(0B3A)
Sets the address of the register that is output to Modbus Reg 1 Status Satisfied [H2-01 to H2-03 = 62] and uses the bit
in H2-08 [Modbus Register 1 Bit Select].
H2-08: Modbus Register 1 Bit Select
No.
Name
(Hex.)
H2-08
Modbus Register 1 Bit
Select
(0B3B)
Sets the bit of the register that is output to Modbus Reg 1 Status Satisfied [H2-01 to H2-03 = 62] and uses the address
in H2-07 [Modbus Register 1 Address Select].
H2-09: Modbus Register 2 Address Select
No.
Name
(Hex.)
H2-09
Modbus Register 2 Address
Select
(0B3C)
Sets H2-09 with the address of the register that is output to Modbus Reg 2 Status Satisfied [H2-01 to H2-03 = 63] and
uses the bit in H2-10 [Modbus Register 2 Bit Select].
H2-10: Modbus Register 2 Bit Select
No.
Name
(Hex.)
H2-10
Modbus Register 2 Bit
Select
(0B3D)
Sets the bit of the register that is output to Modbus Reg 2 Status Satisfied [H2-01 to H2-03 = 63] and uses the address
in H2-09.
H2-20: Comparator 1 Monitor Selection
No.
Name
(Hex.)
H2-20
Comparator 1 Monitor
Selection
(1540)
Note:
• For information on the comparator function, refer to
• The configurable monitor changes when the control method changes.
908
V/f
CL-V/f
OLV
CLV
AOLV
Sets the address of the MEMOBUS/Modbus register output to the MFDO terminal.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the bit of the MEMOBUS/Modbus register output to the MFDO terminal.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the address of the MEMOBUS/Modbus register output to the MFDO terminal.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the bit of the MEMOBUS/Modbus register output to the MFDO terminal.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the monitor number for comparator 1. Set the x-xx part of the Ux-xx [Monitor]. For example, set
H2-20 = 102 to monitor U1-02 [Output Frequency].
66: Comparator1 on page 927
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
and
67: Comparator2 on page
YASKAWA SIEPC71061737D GA800 Drive Technical Reference
Default
(Range)
0001
(0001 - 1FFF)
Default
(Range)
0000
(0000 - FFFF)
Default
(Range)
0001
(0001 - 1FFF)
Default
(Range)
0000
(0000 - FFFF)
Default
(Range)
102
(000 - 999)
928.