YASKAWA GA800 Technical Reference page 603

Ac drive for industrial applications
Hide thumbs Also See for GA800:
Table of Contents

Advertisement

Setting Value
Function
109
!Frequency Reference
from Keypad
10A
!Run Command from
Keypad
10B
Torque Detection 1 (N.C.)
10C
!Frequency Reference
Loss
10D
!Braking Resistor Fault
10E
!Fault
110
!Alarm
111
!Fault Reset Command
Active
112
!Timer Output
113
!Speed Agree 2
114
!User-Set Speed Agree 2
115
!Frequency Detection 3
116
!Frequency Detection 4
117
Torque Detection 1 (N.
O.)
118
Torque Detection 2 (N.C.)
YASKAWA SIEPC71061737D GA800 Drive Technical Reference
V/f
CL-V/f
OLV
CLV
AOLV
Shows the selected frequency reference source.
ON : b1-01 [Frequency Reference Selection 1] or b1-15 [Frequency Reference Selection 2] is the frequency reference
source.
OFF : The keypad is the frequency reference source.
V/f
CL-V/f
OLV
CLV
AOLV
Shows the selected Run command source.
ON : b1-02 [Run Command Selection 1] or b1-16 [Run Command Selection 2] is the Run command source.
OFF : The keypad is the Run command source.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal deactivates when the drive detects overtorque or undertorque.
OFF : The output current/torque exceeds the torque value set with L6-02 [Torque Detection Level 1], or the level has
dropped and remained in this state longer than the time set with L6-03 [Torque Detection Time 1].
V/f
CL-V/f
OLV
CLV
AOLV
The terminal deactivates when the drive detects a loss of frequency reference.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal deactivates when the mounting-type braking resistor is overheating or when there is a braking transistor
fault.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal deactivates when the drive detects a fault.
Note:
Faults CPF00 and CPF01 [Control Circuit Error] are excluded.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal deactivates when the drive detects a minor fault.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal deactivates when the drive receives the Reset command from the control circuit terminal, serial
communications, or the communication option.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the terminal as the timer output. Use this setting with the timer input set in H1-xx = 118 [MFDI Function
Selection = !Timer Function].
V/f
CL-V/f
OLV
CLV
AOLV
The terminal deactivates when the output frequency is in the range of the frequency reference ± L4-04 [Speed Agree
Detection Width(+/-)].
Note:
The drive uses the motor speed as the reference in CLV and CLV/PM.
ON : The output frequency is not in the range of "frequency reference ± L4-04".
OFF : The output frequency is in the range of "frequency reference ± L4-04".
V/f
CL-V/f
OLV
CLV
AOLV
The terminal deactivates when the output frequency is in the range of L4-03 [Speed Agree Detection Level(+/-)] ± L4-
04 [Speed Agree Detection Width(+/-)] and in the range of the frequency reference ± L4-04.
ON : The output frequency is not in the range of "L4-03 ± L4-04" nor the range of frequency reference ± L4-04.
OFF : The output frequency is in the range of "L4-03 ± L4-04" and the range of frequency reference ± L4-04.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal activates when the output frequency is higher than "L4-03 [Speed Agree Detection Level(+/-)] + L4-04
[Speed Agree Detection Width(+/-)]". When the terminal activates, it stays activated until the output frequency = L4-
03.
Note:
• The detection level set in L4-03 is a signed value. Detections only occur one specific orientation.
• The drive uses the motor speed as the reference in CLV and CLV/PM.
ON : The output frequency is higher than L4-03 + L4-04.
OFF : The output frequency is less than L4-03 or is not more than L4-03 + L4-04.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal deactivates when the output frequency is higher than the value of L4-03 [Speed Agree Detection Level
(+/-)]. After the terminal deactivates, the terminal stays deactivated until the output frequency = L4-03 - L4-04.
ON : The output frequency is less than "L4-03 - L4-04," or it is not more than L4-03.
OFF : The output frequency is more than L4-03.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal activates when the drive detects overtorque or undertorque.
ON : The output current/torque exceeds the torque value set with L6-02 [Torque Detection Level 1], or the level has
dropped and remained in this state longer than the time set with L6-03 [Torque Detection Time 1].
V/f
CL-V/f
OLV
CLV
AOLV
The terminal deactivates when the drive detects overtorque or undertorque.
OFF : The output current/torque exceeds the torque value set with L6-05 [Torque Detection Level 2], or the level has
dropped and remained in this state longer than the time set with L6-06 [Torque Detection Time 2].
Description
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
11.10 H: Terminal Functions
Ref.
929
929
929
929
929
929
929
929
929
929
929
929
929
929
929
11
603

Advertisement

Table of Contents
loading

Table of Contents