12.8 H: Terminal Functions
H5-28: Function 5A Register 4 Selection
No.
Name
(Hex.)
H5-28
Function 5A Register 4
Selection
(158C)
RUN

H6: Pulse Train Input/Output

H6 parameters set the drive pulse train input and pulse train monitor. These parameters select input and monitor
parameters and adjust the pulse train frequency.
A pulse train signal with a maximum single pulse of 32 kHz can be input to the drive input terminal RP. You can use
the pulse train signal as the frequency reference, PID feedback value, PID setpoint value, and speed feedback for V/f
Control mode.
A pulse train signal with a maximum frequency of 32 kHz can be output from the drive output terminal MP as the
monitor value. Sinking mode and sourcing mode are supported.
H6-01: Terminal RP Pulse Train Function
No.
Name
(Hex.)
H6-01
Terminal RP Pulse Train
Function
(042C)
0 : Frequency Reference
When b1-01 = 4 [Frequency Reference Selection 1 = Pulse Train Input] or b1-15 = 4 [Frequency Reference Selection
2 = Pulse Train Input], the drive inputs the frequency reference received from terminal RP.
1 : PID Feedback Value
The drive inputs the PID control feedback value received from terminal RP.
2 : PID Setpoint Value
The drive inputs the PID control target value received from terminal RP.
3 : Speed Feedback (V/F Control)
Select V/f Control method to enable simple encoder feedback.
Use motor speed feedback for better speed control precision. The drive compares the frequency reference to the motor
speed feedback received from the encoder, and uses the ASR function to compensates for motor slip. You cannot use
input terminal RP used for the simple encoder to detect the direction of motor rotation. Use a different method to
detect motor rotation.
Use these methods to detect the direction of motor rotation.
• Use MFDI
Set MFDI H1-xx = 7E [Reverse Rotation Identifier]. When the configured terminal is activated, the motor operates
in Reverse run. When the terminal is deactivated, the motor operates in Forward run.
Use an encoder that outputs 2-tracks (phase A, B) to detect the direction of motor rotation.
• Use the frequency reference
When you do not use the MFDI, the Forward/Reverse run command is the same as the direction of motor rotation.
Figure 12.114
shows speed control in Simple Closed Loop V/f Mode.
950
V/f
CL-V/f
OLV
CLV
AOLV
Returns the contents of the specified MEMOBUS/Modbus communications register when responding
to the master device.
Figure 12.113 Pulse Train Input Block Diagram
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function for pulse train input terminal RP.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
YASKAWA SIEPC71061737D GA800 Drive Technical Reference
Default
(Range)
0049H (U1-10)
(0000H - FFFFH)
Default
(Range)
0
(0 - 3)