E3: V/F Pattern For Motor 2 - YASKAWA GA800 Technical Reference

Ac drive for industrial applications
Hide thumbs Also See for GA800:
Table of Contents

Advertisement

12.6 E: Motor Parameters
E2-09: Motor Mechanical Loss
No.
Name
(Hex.)
E2-09
Motor Mechanical Loss
(0316)
Expert
Adjust this parameter in these conditions. The drive adds the configured mechanical loss to the torque reference value
as a torque compensation value:
• There is a large quantity of torque loss from motor bearing friction.
• There is a large quantity of torque loss in fans and pumps.
E2-10: Motor Iron Loss
No.
Name
(Hex.)
E2-10
Motor Iron Loss
(0317)
E2-11: Motor Rated Power
No.
Name
(Hex.)
E2-11
Motor Rated Power
(0318)
The drive automatically sets this parameter to the value input for "Motor Rated Power" during Auto-Tuning.

E3: V/f Pattern for Motor 2

E3 parameters [V/f Pattern for Motor 2] set the control mode and V/f pattern used for motor 2.
Note:
V/f preset patterns equivalent to those set with E1-03 [V/f Pattern Selection] are not available for E3 parameters. Use E3-04 [Motor 2
Maximum Output Frequency] to E3-10 [Motor 2 Minimum Output Voltage] to manually set the V/f pattern.
Notes on Manually Setting V/f Patterns
• To configure a linear V/f pattern at frequencies lower than E3-06 [Motor 2 Base Frequency], set E3-07 = E3-09
[Motor 2 Mid Point A Frequency = Motor 2 Minimum Output Frequency]. In this application, the drive ignores E1-
08 [Mid Point A Voltage].
• Set the five frequencies as specified by these rules:
E3-09 ≤ E3-07 < E3-06 ≤ E3-11 ≤ E3-04 [Motor 2 Minimum Output Frequency ≤ Motor 2 Mid Point A Frequency
< Motor 2 Base Frequency ≤ Motor 2 Mid Point B Frequency ≤ Motor 2 Maximum Output Frequency]
Incorrect settings will trigger oPE10 [V/f Data Setting Error].
• If E3-11 = 0.0 Hz, the drive will ignore the V/f pattern settings.
828
V/f
CL-V/f
OLV
CLV
AOLV
Sets the mechanical loss of the motor. It is set as a percentage of E2-11 [Motor Rated Power].
Usually it is not necessary to change this setting.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the motor iron loss.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the motor rated output in the units from o1-58 [Motor Power Unit Selection].
Figure 12.73 Motor 2 V/f Pattern Diagram
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
YASKAWA SIEPC71061737D GA800 Drive Technical Reference
Default
(Range)
0.0%
(0.0 - 10.0%)
Default
(Range)
Determined by o2-04, C6-01
(0 - 65535 W)
Default
(Range)
Determined by o2-04, C6-01
(0.00 - 650.00)